8.4. Operation Control
8.4.1. Restart Control (Time Delay Safety Control)
•
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
−
Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
−
Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
•
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
•
This phenomenon is to balance the pressure inside the refrigerant cycle.
8.4.2. 7 Minutes Time Save Control
•
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
•
This phenomenon is to reduce the built up humidity inside a room.
8.4.3. 60 Seconds Forced Operation
•
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake
air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
•
The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
8.4.4. Starting Current Control
•
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
•
The reason of the difference is to reduce the starting current flow.
16
CS-MC12DKV CU-2C24DKV
Summary of Contents for CS-MC12DKV
Page 3: ...2 Functions 3 CS MC12DKV CU 2C24DKV ...
Page 4: ...4 CS MC12DKV CU 2C24DKV ...
Page 8: ...4 Dimensions 4 1 Indoor Unit Remote Control 8 CS MC12DKV CU 2C24DKV ...
Page 9: ...4 2 Outdoor Unit 9 CS MC12DKV CU 2C24DKV ...
Page 10: ...5 Refrigeration Cycle Diagram 10 CS MC12DKV CU 2C24DKV ...
Page 11: ...6 Block Diagram 11 CS MC12DKV CU 2C24DKV ...
Page 12: ...7 Wiring Diagram 12 CS MC12DKV CU 2C24DKV ...
Page 26: ...9 Operating Instructions 26 CS MC12DKV CU 2C24DKV ...
Page 27: ...27 CS MC12DKV CU 2C24DKV ...
Page 28: ...28 CS MC12DKV CU 2C24DKV ...
Page 29: ...29 CS MC12DKV CU 2C24DKV ...
Page 30: ...30 CS MC12DKV CU 2C24DKV ...
Page 31: ...31 CS MC12DKV CU 2C24DKV ...
Page 57: ...14 3 Piping Length Characteristic Cooling 57 CS MC12DKV CU 2C24DKV ...
Page 67: ...67 CS MC12DKV CU 2C24DKV ...
Page 69: ...19 1 Remote Control 69 CS MC12DKV CU 2C24DKV ...
Page 70: ...19 2 Print Pattern Indoor Unit Printed Circuit Board 70 CS MC12DKV CU 2C24DKV ...
Page 71: ...71 CS MC12DKV CU 2C24DKV ...