38 

CUTTING AND FLARING THE PIPING 

1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using a reamer. If burrs are not removed, gas leakage may occur.

Turn the piping end down to avoid the metal powder entering the pipe.

3. Please make flare after inserting the flare nut onto the copper pipes.

10.2.4  Evacuation Of The Equipment 

WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND 
PIPES in the following procedure. 

1. Connect a charging hose with a push pin to

the Low side of a charging set and the service
port of the gas side 3-way valve.

2. Connect the micron gauge between vacuum

pump and service port of outdoor units.

3. Turn on the power switch of the vacuum pump

and make sure to connect the digital micron
gauge and to lower to a value of 500 microns.

4. Make sure micron gauge indicates a value of

500 microns and close the low side valve of
the charging set and turn off the vacuum
pump.

5. Disconnect the vacuum pump house from the

service port of the 3-way valve. 

6. Tighten the service port caps of gas side

3-way valve at a torque of 13.3 Ibf•ft (18 N•m)
with a torque wrench. 

7. Remove the valve caps of both the 2-way

valve and 3-way valve. Position both of the
valves to “Open” using a hexagonal wrench
(5/32" (4 mm)).

8. Mount valve caps onto the 2-way valve and

3-way valve.

o

Be sure to check for gas leakage.

š

If micron gauge value does not descend 500 microns, take the following measures:

-

If the leak stops when the piping connections are tightened further, continue working from step 

e

.

-

If the leak does not stop when the connections are retightened, repair location of leak.

-

Do not release refrigerant during piping work for installation and reinstallation.

-

Be careful when handling the liquid refrigerant, it may cause frostbite.

Reamer

2. To remove burrs

Point down

Pipe

1. To cut

Bar

0 –

1

/

32

"

(0-0.5 mm)

Ŷ

Improper flaring

Ŷ

Copper pipe

Inclined Surface

damaged

Cracked Uneven

thickness

3. To flare

Bar

Red arrow mark

Handle

Core

Yoke

Clamp handle

When properly flared, the internal
surface of the flare will shine evenly
and be of even thickness. Since the
flared part comes into contact with
the connections, carefully check the
flared finish.

Outdoor unit

Liquid side

Gas
side

Vacuum

pump

Liquid side 3-way valve

Gas side 3-way valve

Liquid side

Gas
side

Tube connector

Tube connector

Tube connector

Tube connector

Close

Close

Indoor Unit

Indoor Unit

Summary of Contents for CS-KS18NB4UW & CZ-18BT1U + CU-KS18NKU

Page 1: ...placed with manufacturer s specified parts to prevent shock fire or other hazards Do not modify the original design without permission of manufacturer WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical individuals of potential dangers in attempting to...

Page 2: ...S YES YES YES YES YES YES YES YES YES YES NO YES YES CS MKS9NKU CS MKS12NKU CS MKS18NKU CS MKS24NKU Wall Mounted Type CU 3KS19NBU CU 4KS24NBU CU 4KS31NBU Multi Outdoor Unit Indoor Unit 3 Room 4 Room 4 Room CS MKS9NB4U CZ 18BT1U YES YES YES YES YES YES YES YES YES CS MKS12NB4U CZ 18BT1U CS KS18NB4UW CZ 18BT1U Semi Concealed Type 6 ...

Page 3: ... connecting tube kit CZ 3F type Unit A Maximum pipe length 25 m 82 0 ft Unit B Maximum pipe length 25 m 82 0 ft Unit C Maximum pipe length 25 m 82 0 ft Indoor outdoor unit connection cables Flexible cord x 4 core polychloroprene sheathed Not included in the unit Outdoor unit power supply Single phase 208 230V 60Hz 30A switch circuit breaker Not included in the unit Flexible cord x 3 core Not inclu...

Page 4: ...ximum pipe length 25 m 82 0 ft Unit B Maximum pipe length 25 m 82 0 ft Unit C Maximum pipe length 25 m 82 0 ft Unit D Maximum pipe length 25 m 82 0 ft Indoor outdoor unit connection cables Flexible cord x 4 core polychloroprene sheathed Not included in the unit Flexible cord x 4 core polychloroprene sheathed Outdoor unit power supply Single phase 208 230V 60Hz 45A switch circuit breaker Not includ...

Page 5: ...h Outdoor Unit CU 3E19 Allowable piping length of each indoor unit min max 9 8 ft 82 0 ft 3 m 25 m Allowable total piping length of all indoor unit 164 0 ft 50 m or less Height difference between indoor and outdoor unit Outdoor unit located on upper side g 49 2 ft 15 m or less Outdoor unit located otherwise h 24 6 ft 7 5 m or less Outdoor unit located otherwise k 49 2 ft 15 m or less Height differ...

Page 6: ... the copper pipe Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table Do not over tighten over tightening may cause gas leakage Piping size Torque 1 4 6 35 mm 13 3 Ibf ft 18 N m 1 8 kgf m 3 8 9 52 mm 31 0 Ibf ft 42 N m 4 3 kgf m 1 2 12 7 mm 40 6 Ibf ft 55 N m 5 6 kgf m 5 8 15 88 mm 47 9 Ibf ft 65 N m 6 6 kgf m 3 4 19 05 mm 73 8 Ibf ft ...

Page 7: ...3 3 Ibf ft 18 N m with a torque wrench 7 Remove the valve caps of both of the 2 way valve and 3 way valve Position both of the valves to Open using a hexagonal wrench 5 32 4 mm 8 Mount valve caps onto the 2 way valve and 3 way valve o Be sure to check for gas leakage If micron gauge value does not descend 500 microns take the following measures If the leak stops when the piping connections are tig...

Page 8: ...nit A Unit C Terminal Terminal Indoor Unit B Indoor Unit A Disconnect Switch Field supply Grounding wire Grounding wire min AWG16 Grounding wire min AWG16 Grounding wire min AWG16 Power Supply Single Phase 208 230V 60Hz min AWG12 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16...

Page 9: ...aterial shall withstand 248 F 120 C or higher Gas side pipes 10 1 7 Disposal Of Outdoor Unit Drain Water If a drain elbow is used the unit should be placed on a stand which is taller than 1 31 32 50 mm If the unit is used in an area where temperature falls below 32 F 0 C for 2 or 3 days in succession it is recommended not to use a drain elbow for the drain water freezes and the fan will not rotate...

Page 10: ...tdoor Unit Installation Diagram Allowable piping length Outdoor Unit CU 4E24 Allowable piping length of each indoor unit min max 9 8 ft 82 0 ft 3 m 25 m Allowable total piping length of all indoor unit 229 6 ft 70 m or less Height difference between indoor and outdoor unit Outdoor unit located on upper side g 49 2 ft 15 m or less Outdoor unit located otherwise h 24 6 ft 7 5 m or less Outdoor unit ...

Page 11: ...wrench to the specified torque as stated in the table Do not over tighten over tightening may cause gas leakage Piping size Torque 1 4 6 35 mm 13 3 Ibf ft 18 N m 1 8 kgf m 3 8 9 52 mm 31 0 Ibf ft 42 N m 4 3 kgf m 1 2 12 7 mm 40 6 Ibf ft 55 N m 5 6 kgf m 5 8 15 88 mm 47 9 Ibf ft 65 N m 6 6 kgf m 3 4 19 05 mm 73 8 Ibf ft 100 N m 10 2 kgf m Gas Leak Checking Pressure test to system to 400 PSIG with d...

Page 12: ...of 13 3 Ibf ft 18 N m with a torque wrench 7 Remove the valve caps of both the 2 way valve and 3 way valve Position both of the valves to Open using a hexagonal wrench 5 32 4 mm 8 Mount valve caps onto the 2 way valve and 3 way valve o Be sure to check for gas leakage If micron gauge value does not descend 500 microns take the following measures If the leak stops when the piping connections are ti...

Page 13: ...ng wire Power Supply Single Phase 208 230V 60Hz min AWG12 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Indoor Unit B ...

Page 14: ...aterial shall withstand 248 F 120 C or higher Gas side pipes 10 2 7 Disposal Of Outdoor Unit Drain Water If a drain elbow is used the unit should be placed on a stand which is taller than 1 31 32 50 mm If the unit is used in an area where temperature falls below 32 F 0 C for 2 or 3 days in succession it is recommended not to use a drain elbow for the drain water freezes and the fan will not rotate...

Reviews: