background image

32 

Outdoor Unit Installation Guidelines 

š

Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation
guidelines below.

š

For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4" (1200 mm) or
less.

10.1.2  Install The Outdoor Unit

š

After selecting the best location, start installation
to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly

and horizontally by bolt nut (ø13/32"
(ø10 mm)).

2. When installing on a roof, please consider

strong winds and earthquakes.

3. Please fasten the installation stand firmly with

bolt or nails.

Model

A

B

C

D

CU-3E19*** 

24-1/8"

(613 mm)

5-5/32"

(131 mm)

5/8" 

(16 mm) 

14-3/16"

(360.5 mm)

10.1.3  Connect The Piping

š

Remove the control board cover (resin) from the
outdoor unit by loosening three screws.

Connecting The Piping To Outdoor Unit 

Decide piping length and then cut by using pipe cutter. 
Remove burrs from cut edge. Make flare after 
inserting the flare nut (locate at valve) onto the copper 
pipe. 
Align center of piping to valves and then tighten with 
torque wrench to the specified torque as stated in the 
table. 

Do not over tighten, over tightening may cause gas leakage 

Piping size 

Torque 

1/4" [6.35 mm] 

13.3 Ibf•ft [18 N•m (1.8 kgf•m)] 

3/8" [9.52 mm] 

31.0 Ibf•ft [42 N•m (4.3 kgf•m)] 

1/2" [12.7 mm] 

40.6 Ibf•ft [55 N•m (5.6 kgf•m)] 

5/8" [15.88 mm] 

47.9 Ibf•ft [65 N•m (6.6 kgf•m)] 

3/4" [19.05 mm] 

73.8 Ibf•ft [100 N•m (10.2 kgf•m)] 

Gas Leak Checking 

Pressure test to system to 400 PSIG with dry nitrogen, 
in stages. Thoroughly leak check the system. 
If the pressure holds, release the nitrogen and 
proceed to section 10.1.4.

 

Wall facing one side

More than 3 15/16" (100)

w

e

i

v

p

o

T

w

e

i

v

e

d

i

S

47 1/4" (1200)

or less

More than
39 3/8" (1000)

More than
39 3/8" (1000)

More than
3 15/16" (100)

More than
3 15/16" (100)

More
than
3 15/16"
(100)

More than
3 15/16" (100)

More than
39 3/8" (1000)

More than
11 13/16" (300)

Walls facing two side

Walls facing three side

Top view

Unit : inch (mm)

A

B

C

D

 

Screw

Screws

Control Board Cover (Resin)

Flare Nut

Torque Wrench for Flare Nut

(Connection Pipe)

(Connection Pipe)

Male side

Female side

Applicable to 
Liquid and Gas side of
CS-ME5***    CS-E12***
CS-ME7***    CS-E18***
CS-E9***

Torque Wrench for Flare Nut

Liquid side

Gas side

Flare Nut

Summary of Contents for CS-KS18NB4UW & CZ-18BT1U + CU-KS18NKU

Page 1: ...placed with manufacturer s specified parts to prevent shock fire or other hazards Do not modify the original design without permission of manufacturer WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical individuals of potential dangers in attempting to...

Page 2: ...S YES YES YES YES YES YES YES YES YES YES NO YES YES CS MKS9NKU CS MKS12NKU CS MKS18NKU CS MKS24NKU Wall Mounted Type CU 3KS19NBU CU 4KS24NBU CU 4KS31NBU Multi Outdoor Unit Indoor Unit 3 Room 4 Room 4 Room CS MKS9NB4U CZ 18BT1U YES YES YES YES YES YES YES YES YES CS MKS12NB4U CZ 18BT1U CS KS18NB4UW CZ 18BT1U Semi Concealed Type 6 ...

Page 3: ... connecting tube kit CZ 3F type Unit A Maximum pipe length 25 m 82 0 ft Unit B Maximum pipe length 25 m 82 0 ft Unit C Maximum pipe length 25 m 82 0 ft Indoor outdoor unit connection cables Flexible cord x 4 core polychloroprene sheathed Not included in the unit Outdoor unit power supply Single phase 208 230V 60Hz 30A switch circuit breaker Not included in the unit Flexible cord x 3 core Not inclu...

Page 4: ...ximum pipe length 25 m 82 0 ft Unit B Maximum pipe length 25 m 82 0 ft Unit C Maximum pipe length 25 m 82 0 ft Unit D Maximum pipe length 25 m 82 0 ft Indoor outdoor unit connection cables Flexible cord x 4 core polychloroprene sheathed Not included in the unit Flexible cord x 4 core polychloroprene sheathed Outdoor unit power supply Single phase 208 230V 60Hz 45A switch circuit breaker Not includ...

Page 5: ...h Outdoor Unit CU 3E19 Allowable piping length of each indoor unit min max 9 8 ft 82 0 ft 3 m 25 m Allowable total piping length of all indoor unit 164 0 ft 50 m or less Height difference between indoor and outdoor unit Outdoor unit located on upper side g 49 2 ft 15 m or less Outdoor unit located otherwise h 24 6 ft 7 5 m or less Outdoor unit located otherwise k 49 2 ft 15 m or less Height differ...

Page 6: ... the copper pipe Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table Do not over tighten over tightening may cause gas leakage Piping size Torque 1 4 6 35 mm 13 3 Ibf ft 18 N m 1 8 kgf m 3 8 9 52 mm 31 0 Ibf ft 42 N m 4 3 kgf m 1 2 12 7 mm 40 6 Ibf ft 55 N m 5 6 kgf m 5 8 15 88 mm 47 9 Ibf ft 65 N m 6 6 kgf m 3 4 19 05 mm 73 8 Ibf ft ...

Page 7: ...3 3 Ibf ft 18 N m with a torque wrench 7 Remove the valve caps of both of the 2 way valve and 3 way valve Position both of the valves to Open using a hexagonal wrench 5 32 4 mm 8 Mount valve caps onto the 2 way valve and 3 way valve o Be sure to check for gas leakage If micron gauge value does not descend 500 microns take the following measures If the leak stops when the piping connections are tig...

Page 8: ...nit A Unit C Terminal Terminal Indoor Unit B Indoor Unit A Disconnect Switch Field supply Grounding wire Grounding wire min AWG16 Grounding wire min AWG16 Grounding wire min AWG16 Power Supply Single Phase 208 230V 60Hz min AWG12 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16...

Page 9: ...aterial shall withstand 248 F 120 C or higher Gas side pipes 10 1 7 Disposal Of Outdoor Unit Drain Water If a drain elbow is used the unit should be placed on a stand which is taller than 1 31 32 50 mm If the unit is used in an area where temperature falls below 32 F 0 C for 2 or 3 days in succession it is recommended not to use a drain elbow for the drain water freezes and the fan will not rotate...

Page 10: ...tdoor Unit Installation Diagram Allowable piping length Outdoor Unit CU 4E24 Allowable piping length of each indoor unit min max 9 8 ft 82 0 ft 3 m 25 m Allowable total piping length of all indoor unit 229 6 ft 70 m or less Height difference between indoor and outdoor unit Outdoor unit located on upper side g 49 2 ft 15 m or less Outdoor unit located otherwise h 24 6 ft 7 5 m or less Outdoor unit ...

Page 11: ...wrench to the specified torque as stated in the table Do not over tighten over tightening may cause gas leakage Piping size Torque 1 4 6 35 mm 13 3 Ibf ft 18 N m 1 8 kgf m 3 8 9 52 mm 31 0 Ibf ft 42 N m 4 3 kgf m 1 2 12 7 mm 40 6 Ibf ft 55 N m 5 6 kgf m 5 8 15 88 mm 47 9 Ibf ft 65 N m 6 6 kgf m 3 4 19 05 mm 73 8 Ibf ft 100 N m 10 2 kgf m Gas Leak Checking Pressure test to system to 400 PSIG with d...

Page 12: ...of 13 3 Ibf ft 18 N m with a torque wrench 7 Remove the valve caps of both the 2 way valve and 3 way valve Position both of the valves to Open using a hexagonal wrench 5 32 4 mm 8 Mount valve caps onto the 2 way valve and 3 way valve o Be sure to check for gas leakage If micron gauge value does not descend 500 microns take the following measures If the leak stops when the piping connections are ti...

Page 13: ...ng wire Power Supply Single Phase 208 230V 60Hz min AWG12 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Indoor Unit B ...

Page 14: ...aterial shall withstand 248 F 120 C or higher Gas side pipes 10 2 7 Disposal Of Outdoor Unit Drain Water If a drain elbow is used the unit should be placed on a stand which is taller than 1 31 32 50 mm If the unit is used in an area where temperature falls below 32 F 0 C for 2 or 3 days in succession it is recommended not to use a drain elbow for the drain water freezes and the fan will not rotate...

Reviews: