9.15.8. Four-way valve Operation Detection Control (Switching Abnormality between
Cooling and Heating)
In Cooling operation
1. When indoor heat exchanger temperature exceeds 45°C in 4 minutes after compressor starts, compressor will be stopped.
2. If the above excess occurs 4 times per 30 minutes, timer lamp is to be blinking. (“F11” is to be confirmed.)
In Heating operation
1. When indoor heat exchanger temperature is below 0°C in 4 minutes after compressor starts, compressor will be stopped.
2. If the above excess occurs 4 times per 30 minutes, timer lamp is to be blinking. (“F11” is to be confirmed.)
9.15.9. Anti-Freezing Control (Cooling and Dry operations)
Limit of Cooling power
1. When temperature of indoor heat exchanger is below 5°C, operating frequency will be decreased.
2. When temperature of indoor heat exchanger exceeds 7°C, operating frequency will be increased. (But, up to programmed
frequency.)
3. When temperature of indoor heat exchanger is below 0°C continuously for 6 minutes, compressor will be stopped.
4. Timer lamp is not blinking. (“F99” is memorized, then.)
Limit of Indoor fan speed
•
•
•
•
When temperature of indoor heat exchanger is below 6°C (2°C at Dry) continuously for 6 minutes, indoor fan speed will be
increased by 50 rpm.
9.15.10. Outdoor Air Temperature Control
In Cooling and Dry operations
1. When outdoor air temperature is below 25°C, the maximum power will be limited up to about 80-100% of the rated power.
2. When outdoor air temperature is below 18°C, the maximum power will be limited up to about 50-100% of the rated power.
3. When outdoor air temperature is below 11°C, the maximum power will be limited up to about 26-81% of the rated power.
9.15.11. Indoor Intake Air Temperature Control (Heating operation)
1. When indoor air temperature is 35°C or more, the maximum power will be limited up to the rated power.
2. When fan speed is set at "Lo" and intake air temperature is below 21°C, the maximum power will be limited up to the rated
power.
38
CS-HE9DKE CU-HE9DKE / CS-HE12DKE CU-HE12DKE
Summary of Contents for CS-HE9DKE
Page 3: ...2 Functions 2 1 Remote Control 3 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 4: ...2 2 Indoor Unit 4 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 5: ...2 3 Outdoor unit 5 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 10: ...4 Dimensions 4 1 Indoor Unit Remote Control 10 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 11: ...4 2 Outdoor Unit 11 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 12: ...5 Refrigeration Cycle Diagram 12 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 13: ...6 Block Diagram 13 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 14: ...7 1 Indoor Unit 7 Wiring Diagram 14 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 15: ...7 2 Outdoor Unit 15 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 17: ...17 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 18: ...8 2 Outdoor Unit 18 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 19: ...19 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 39: ...10 Operating Instructions 39 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 40: ...40 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 41: ...41 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 42: ...42 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 43: ...43 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 44: ...44 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 82: ...CS HE12DKE CU HE12DKE 82 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...