9.15.1. Time Delay Safety Control
9.15. Protection Control
•
•
•
•
Compressor will not start for two minutes after stop of the operation.
9.15.2. 30 Seconds Forced Operation
•
•
•
•
Once compressor starts the operation, it will not stop its operation for 30 seconds. However, it can be stopped with the remote
controller or the Auto button on the indoor unit.
9.15.3. Total Running Current Control
1. When the total running current exceeds I1, compressor operation frequency is reduced. If it reaches below I1, the operation
frequency is increased. (But, up to programmed frequency.)
2. If total running current exceeds I2, compressor is stopped immediately.
3. If it happens three (3) times within 20 minutes, operation will be stopped and Timer LED blinks. (“F98” is activating.)
Running current
CS-HE9DKE
CS-HE12DKE
Cooling
I1
4.5A
5.8A
I2
12.5A
12.5A
Heating
I1
7.2A
9.6A
I2
12.5A
12.5A
9.15.4. IPM (Power transistor) Protection Control (DC Peak detection)
Abnormal Current Control
•
•
•
•
If inverter load current (DC peak) exceeds a rated value, compressor will be stopped immediately. When the excess
occurs within 30 seconds after operation, it restarts in 1 minute and when after 30 seconds, restarts in 2 minutes.
•
•
•
•
If the excess continuously occurs 7 times within 30 minutes after compressor starts, the unit will be stopped and timer
lamp on the indoor unit will be blinking. (“F99” is to be confirmed.)
IPM Overheating Prevention Control
•
•
•
•
If temperature of IPM exceeds 103°C, compressor will be stopped. It will restart in 2 minutes. Temperature for restarting:
90°C.
•
•
•
•
If the excess occurs 4 times within 30 minutes after compressor starts, the compressor will be stopped and timer lamp
on the indoor unit will be blinking. (“F96” is to be confirmed.)
9.15.5. Compressor Overheating Prevention Control
1. If discharge pipe temperature exceeds 100°C, compressor power will be limited.
2. If discharge pipe temperature exceeds 112°C, compressor will be stopped.
3. If the above excess occurs 4 times per 10 minutes, timer lamp will be blinking. (“F97” is to be confirmed.)
9.15.6. Outdoor High Pressure Prevention Control (Cooling and Dry operations)
1. If outdoor heat exchanger temperature exceeds 63°C in cooling or dry operation, compressor will be stopped.
2. Timer lamp is not blinking. (“F95” is memorized, then.)
9.15.7. Compressor Protection Control (Refrigeration Cycle Abnormality)
In Cooling and Dry operations
1. When compressor is operated continuously for 5 minutes in the maximum cooling power: a running current of 0.6 - 1.2A
(excl.) and “[Indoor intake air temperature] - [Indoor heat exchanger temperature]” < 4°C, compressor will be stopped.
2. If the above excess occurs twice for 20 minutes, timer lamp is to be blinking. (“F91” is to be confirmed.)
In Heating operation
1. When compressor is operated continuously for 5 minutes in the rated heating power: a running current of 0.6 - 1.2A (excl.)
and “[Indoor heat exchanger temperature] - [Indoor intake air temperature]” < 5°C, compressor will be stopped.
2. If the above excess occurs twice for 20 minutes, timer lamp is to be blinking. (“F91” is to be confirmed.)
37
CS-HE9DKE CU-HE9DKE / CS-HE12DKE CU-HE12DKE
Summary of Contents for CS-HE9DKE
Page 3: ...2 Functions 2 1 Remote Control 3 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 4: ...2 2 Indoor Unit 4 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 5: ...2 3 Outdoor unit 5 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 10: ...4 Dimensions 4 1 Indoor Unit Remote Control 10 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 11: ...4 2 Outdoor Unit 11 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 12: ...5 Refrigeration Cycle Diagram 12 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 13: ...6 Block Diagram 13 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 14: ...7 1 Indoor Unit 7 Wiring Diagram 14 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 15: ...7 2 Outdoor Unit 15 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 17: ...17 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 18: ...8 2 Outdoor Unit 18 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 19: ...19 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 39: ...10 Operating Instructions 39 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 40: ...40 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 41: ...41 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 42: ...42 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 43: ...43 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 44: ...44 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...
Page 82: ...CS HE12DKE CU HE12DKE 82 CS HE9DKE CU HE9DKE CS HE12DKE CU HE12DKE...