14.4. Error Codes Table
Note:
“O” - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard
following by pressing the “CHECK” button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is
changed from one “beep” to four “beep” sounds.
Abnormality / Protection control
Abnormality
Judgement
Emergency
operation
Primary location to verify
Diagnosis
display
H00
No abnormality detected
—
Normal operation
—
H11
Indoor / outdoor abnormal
communication
> 1 min after starting
operation
Indoor fan operation
only
• Internal / external cable connections
• Indoor / Outdoor PCB
H14
Indoor intake air temperature sensor
abnormality
Continue for 5 sec.
—
• Intake air temperature sensor
(defective or disconnected)
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
—
• Compressor temperature sensor
(defective or disconnected)
H16
Outdoor Current Transformer open
circuit
—
—
• Outdoor PCB
• IPM (Power transistor) module
H19
Indoor fan motor merchanism lock
—
—
• Indoor PCB
• Fan motor
H23
Indoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
O
(Cooling only)
• Heat exchanger temperature sensor
(defective or disconnected)
H24
Indoor heat exchanger temperature
sensor 2 abnormality
Continue for 5 sec.
—
• Heat exchanger temperature sensor 2
(defective or disconnected)
H26
Ion abnormality
—
—
• Indoor PCB
• Ionizer
H27
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
O
• Outdoor temperature sensor
(defective or disconnected)
H28
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
O
• Outdoor heat exchanger temperature
sensor (defective or disconnected)
H30
Discharge temperature sensor
abnormality
Continue for 5 sec.
—
• Discharge temperature sensor
H33
Indoor/Outdoor wrong connection
—
—
• Indoor/Outdoor supply voltage
H38
Indoor/Outdoor mismatch (brand code)
—
—
—
H97
Outdoor Fan Motor lock abnormality
2 times occurance
within 30 minutes
—
• Outdoor PCB
• Outdoor Fan Motor
H98
Indoor high pressure protection
—
—
• Air filter dirty
• Air circulation short circuit
H99
Indoor heat exchanger anti-freezing pro-
tection
—
—
• Insufficient refrigerant
• Air filter dirty
F11
Cooling / Heating cycle changeover
abnormality
4 times occurance
within 30 minutes
—
• 4-way valve
• V-coil
F90
PFC control
4 times occurance
within 10 minutes
—
• Voltage at PFC
F91
Refrigeration cycle abnormality
2 times occurance
within 20 minutes
—
• No refrigerant
(3-way valve is closed)
F93
Outdoor compressor abnormal revolution
4 times occurance
within 20 minutes
—
• Outdoor compressor
F95
Cool high pressure protection
4 times occurance
within 20 minutes
—
• Outdoor refrigerant circuit
F96
IPM (power transistor) overheating
protection
—
—
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
F97
Outdoor compressor overheating
protection
4 times occurance
within 10 minutes
—
• Insufficient refrigerant
• Compressor
F98
Total running current protection
3 times occurance
within 20 minutes
—
• Excess refrigerant
• Improper heat radiation
F99
Outdoor Direct Current (DC) peak
detection
7 times occurance
continuously
—
• Outdoor PCB
• IPM (Power transistor)
• Compressor
Summary of Contents for CS-E15EKEA
Page 13: ...13 4 2 Outdoor Unit 4 3 Remote Control ...
Page 14: ...14 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS E15EKEA ...
Page 15: ...15 5 1 2 CS E18EKEA CS E21EKEA ...
Page 16: ...16 5 2 Outdoor Unit ...
Page 18: ...18 7 Block Diagram ...
Page 19: ...19 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 20: ...20 8 2 Outdoor Unit ...
Page 21: ...21 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Page 22: ...22 ...
Page 23: ...23 9 1 2 Power Printed Circuit Board ...
Page 24: ...24 ...
Page 25: ...25 9 2 Outdoor Unit ...
Page 26: ...26 ...
Page 29: ...29 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Page 35: ...35 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Page 55: ...55 ...
Page 56: ...56 15 2 Indoor Cross Flow Fan and Fan Motor ...
Page 57: ...57 ...
Page 60: ...60 ...
Page 62: ...62 ...
Page 64: ...64 ...
Page 66: ...66 ...
Page 68: ...68 ...
Page 70: ...70 ...
Page 72: ...72 ...
Page 74: ...74 ...
Page 76: ...76 ...
Page 78: ...78 ...
Page 80: ...80 ...
Page 82: ...82 ...