46
• Control contents:
Outdoor fan speed (switch to zone A and B minimum fan speed).
Outdoor total current (zone C) higher than the specified.
• Cancellation condition: When one of above is not satisfied.
12.2.3.
Freeze Prevention Control
1. When indoor heat exchanger temperature is lower than 2
°
C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10
°
C.
3. At the same time, indoor fan speed in40 rpm compared to its normal operation.
4. If indoor heat exchanger temperature is higher than 10
°
C for five minutes, the fan speed will return to its normal operation.
12.3. Protection Control For Heating Operation
12.3.1.
Intake Air Temperature Control
Compressor will operate at rated freq. or less respectively if either one of the below conditions occur:
1. When the indoor intake air temperature is above 10
°
C and remote control setting fan speed is lower Me-.
2. When the indoor intake air temperature is 30
°
C or above.
12.3.2.
Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the below figures. This
control will begin one minute after the compressor starts.
Summary of Contents for CS-E15EKEA
Page 13: ...13 4 2 Outdoor Unit 4 3 Remote Control ...
Page 14: ...14 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS E15EKEA ...
Page 15: ...15 5 1 2 CS E18EKEA CS E21EKEA ...
Page 16: ...16 5 2 Outdoor Unit ...
Page 18: ...18 7 Block Diagram ...
Page 19: ...19 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 20: ...20 8 2 Outdoor Unit ...
Page 21: ...21 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Page 22: ...22 ...
Page 23: ...23 9 1 2 Power Printed Circuit Board ...
Page 24: ...24 ...
Page 25: ...25 9 2 Outdoor Unit ...
Page 26: ...26 ...
Page 29: ...29 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Page 35: ...35 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Page 55: ...55 ...
Page 56: ...56 15 2 Indoor Cross Flow Fan and Fan Motor ...
Page 57: ...57 ...
Page 60: ...60 ...
Page 62: ...62 ...
Page 64: ...64 ...
Page 66: ...66 ...
Page 68: ...68 ...
Page 70: ...70 ...
Page 72: ...72 ...
Page 74: ...74 ...
Page 76: ...76 ...
Page 78: ...78 ...
Page 80: ...80 ...
Page 82: ...82 ...