28
10.1.3.
Indoor Unit
10.1.3.1. HOW TO FIX INSTALLATION
PLATE
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 680 mm
at right and 570 mm at left of the wall.
The distance from installation plate edge to ceiling should more
than 73 mm.
From installation plate left edge to unit’s left side is 20 mm.
From installation plate right edge to unit’s right is 130 mm.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the left and right side of the installation
plate. The meeting point of the extended line is the
centre of the hole. Another method is by putting
measuring tape at position as shown in the diagram
above. The hole centre is obtained by measuring the
distance namely 140 mm and 155 mm for left and right
hole respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
10.1.3.2. TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking com-
pound at the final stage.
10.1.3.3. INDOOR UNIT INSTALLATION
1. For the right rear piping
2. For the right and right bottom piping
: For left side piping, piping connection for liquid should be about
155 mm from this line.
: For left side piping, piping connection for gas should be about
190 mm from this line.
: For left side piping, piping connection cable should be about
1100 mm from this line.
Caution
When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
Summary of Contents for CS-E15EKEA
Page 13: ...13 4 2 Outdoor Unit 4 3 Remote Control ...
Page 14: ...14 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS E15EKEA ...
Page 15: ...15 5 1 2 CS E18EKEA CS E21EKEA ...
Page 16: ...16 5 2 Outdoor Unit ...
Page 18: ...18 7 Block Diagram ...
Page 19: ...19 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 20: ...20 8 2 Outdoor Unit ...
Page 21: ...21 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Page 22: ...22 ...
Page 23: ...23 9 1 2 Power Printed Circuit Board ...
Page 24: ...24 ...
Page 25: ...25 9 2 Outdoor Unit ...
Page 26: ...26 ...
Page 29: ...29 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Page 35: ...35 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Page 55: ...55 ...
Page 56: ...56 15 2 Indoor Cross Flow Fan and Fan Motor ...
Page 57: ...57 ...
Page 60: ...60 ...
Page 62: ...62 ...
Page 64: ...64 ...
Page 66: ...66 ...
Page 68: ...68 ...
Page 70: ...70 ...
Page 72: ...72 ...
Page 74: ...74 ...
Page 76: ...76 ...
Page 78: ...78 ...
Page 80: ...80 ...
Page 82: ...82 ...