66
14.2
Protection Control For Cooling & Soft Dry Operation
14.2.1 Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor
frequency will adjust base on outdoor air temperature.
14.2.2 Cooling Overload Control
Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation
frequency).
The compressor stop if outdoor pipe temperature exceeds 61°C (E7 ~ 15NK) and 63°C (E18NK).
If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95 indicated: outdoor high pressure rise
protection).
14.2.3 Freeze Prevention Control 1
When indoor heat exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stop
operating.
Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 5°C.
At the same time, indoor fan speed will be higher than during its normal operation.
If indoor heat exchanger temperature is higher than 5°C for 5 minutes, the fan speed will return to its normal
operation.
14.2.4 Freeze Prevention Control 2
Control start conditions
o
During Cooling operation and soft dry operation
During thermo OFF condition, indoor intake temperature is less than 10°C or
Compressor stops for freeze prevention control
o
Either one of the conditions above occurs 5 times in 60 minutes.
Control
contents
o
Operation
stops
o
Timer LED blinks and “H99” indicated
14.2.5 Dew Prevention Control 1
To prevent dew formation at indoor unit discharge area.
This control will be activated if:
o
Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled.
o
When Cooling or Dry mode is operated more than 20 minutes or more.
This control stopped if:
o
Compressor
stopped.
o
Remote control setting changed (fan speed / temperature).
o
Outdoor air temperature and indoor intake temperature changed.
Fan speed will be adjusted accordingly in this control.
Summary of Contents for CS-E12NKDW
Page 15: ...15 Outdoor Unit U 2E15GBE Outdoor Unit U 2E18CBPG ...
Page 16: ...16 Outdoor Unit U 3E18JBE ...
Page 17: ...17 Outdoor Unit U 4E23JBE ...
Page 18: ...18 ...
Page 20: ...20 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 21: ...21 5 Dimensions 5 1 Indoor Unit 5 1 1 CS E7NK CS E9NK CS E12NK CS E15NK ...
Page 22: ...22 5 1 2 CS E18NK ...
Page 23: ...23 5 2 Outdoor Unit 5 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD 5 2 2 CU E18NKD ...
Page 24: ...24 6 Refrigeration Cycle Diagram 6 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 25: ...25 6 2 CU E18NKD ...
Page 26: ...26 7 Block Diagram 7 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 27: ...27 7 2 CU E18NKD ...
Page 29: ...29 8 1 2 CS E18NKDW ...
Page 30: ...30 8 2 Outdoor Unit 8 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 31: ...31 8 2 2 CU E18NKD ...
Page 33: ...33 9 1 2 CS E18NKDW ...
Page 34: ...34 9 2 Outdoor Unit 9 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 35: ...35 9 2 2 CU E18NKD ...
Page 36: ...36 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 38: ...38 10 1 5 Human Activity Sensor Printed Circuit Board ...
Page 39: ...39 10 2 Outdoor Unit 10 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 40: ...40 10 2 2 CU E18NKD ...
Page 73: ...73 16 3 Error Code Table ...
Page 74: ...74 ...
Page 105: ...105 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Page 107: ...107 Figure 9 Figure 10 ...
Page 109: ...109 Figure 14 Figure 15 17 2 1 4 To remove discharge grille Figure 16 ...
Page 111: ...111 Figure 20 Figure 21 ...