41
11. Installation
Instruction
11.1 Select the Best Location
11.1.1 Indoor
Unit
Do not install the unit in excessive oil fume area
such as kitchen, workshop and etc.
There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Recommended installation height for indoor unit
shall be at least 2.5 m.
11.1.2 Outdoor
Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Piping size
Model
Horse
Power
(HP)
Gas Liquid
Std.
Leng-
th
(m)
Max.
Eleva-
tion
(m)
Min.
Piping
Length
(m)
Max.
Piping
Length
(m)
Addi-
tional
Refri-
gerant
(g/m)
Pi-
ping
Leng-
th for
add.
gas
(m)
E7*** 3/4HP
15
15 20 7.5
E9*** 1.0HP
15
15 20 7.5
E12*** 1.5HP
9.52mm
(3/8”)
15 15
20
7.5
E15*** 1.75HP
15
15
20 7.5
E18*** 2.0HP
12.7mm
(1/2”)
15 20
20
7.5
E24*** 2.5HP
20
30 30 10
E28*** 3.0HP
15.88mm
(5/8”)
6.35mm
(1/4")
5
20
3
30 30 10
Example: For E9***
If the unit is installed at 10 m distance, the quantity of
additional refrigerant should be 50 g .... (10-7.5) m x
20 g/m = 50 g.
11.1.3 Indoor/Outdoor Unit Installation
Diagram
Summary of Contents for CS-E12NKDW
Page 15: ...15 Outdoor Unit U 2E15GBE Outdoor Unit U 2E18CBPG ...
Page 16: ...16 Outdoor Unit U 3E18JBE ...
Page 17: ...17 Outdoor Unit U 4E23JBE ...
Page 18: ...18 ...
Page 20: ...20 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 21: ...21 5 Dimensions 5 1 Indoor Unit 5 1 1 CS E7NK CS E9NK CS E12NK CS E15NK ...
Page 22: ...22 5 1 2 CS E18NK ...
Page 23: ...23 5 2 Outdoor Unit 5 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD 5 2 2 CU E18NKD ...
Page 24: ...24 6 Refrigeration Cycle Diagram 6 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 25: ...25 6 2 CU E18NKD ...
Page 26: ...26 7 Block Diagram 7 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 27: ...27 7 2 CU E18NKD ...
Page 29: ...29 8 1 2 CS E18NKDW ...
Page 30: ...30 8 2 Outdoor Unit 8 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 31: ...31 8 2 2 CU E18NKD ...
Page 33: ...33 9 1 2 CS E18NKDW ...
Page 34: ...34 9 2 Outdoor Unit 9 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 35: ...35 9 2 2 CU E18NKD ...
Page 36: ...36 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 38: ...38 10 1 5 Human Activity Sensor Printed Circuit Board ...
Page 39: ...39 10 2 Outdoor Unit 10 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD ...
Page 40: ...40 10 2 2 CU E18NKD ...
Page 73: ...73 16 3 Error Code Table ...
Page 74: ...74 ...
Page 105: ...105 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Page 107: ...107 Figure 9 Figure 10 ...
Page 109: ...109 Figure 14 Figure 15 17 2 1 4 To remove discharge grille Figure 16 ...
Page 111: ...111 Figure 20 Figure 21 ...