37
b. Patrol operation stop condition
When any of the following condition is fulfilled:
• When “OFF/ON” button is pressed.
• During any operation with Patrol, “Patrol” button is pressed again.
• When “e-ion” button is pressed.
• When OFF Timer activates.
c. Patrol operation disable
• To disable the Patrol Operation during unit start (default) with “OFF/ON” button, press “Patrol” button and hold for 5 seconds,
then release.
• To disable the Patrol Operation, press “Patrol” button and hold for 15 seconds, then release.
C. Control Content
a. Gas Sensor Control
• First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness level is monitored.
The Air Dirtiness level is set to level 2.
• After that, gas sensor starts to record the resistance value at fixed interval. Higher resistance value indicates cleaner air.
• The air dirtiness level is monitored by comparing the current resistance value with maximum resistance value from time to time
to get the Air Dirtiness Value.
• There are 3 air dirtiness levels, based on the Air Dirtiness Value:
- Air Dirtiness level 0: Clean
- Air Dirtiness level 1: Moderate
- Air Dirtiness level 2: Contaminated
• Dirtiness level sensitivity adjustment
It is possible to change the gas sensor sensitivity, where the Threshold value (G1 ~ G4) will be shifted accordingly:
1. Press and release “SET” buttton.
2. Press “Timer increment” / “Timer decrement” button to select sensitivity. (Low
Standard (Default)
High)
3. Confirm setting by pressing “Timer Set” button. LCD returned to original display after 2 seconds.
4. LCD returned to original display if remote control does not operate for 30 seconds.
b. e-ion Control
• When dirtiness level is 1 or 2, e-ion operation starts.
• If dirtiness level improves from level 2 to level 1, the unit carries out level change after 60 seconds.
• When dirtiness level returns to level 0 continuously for 10 minutes or more, e-ion operation stops.
Dirtiness Level Shift
• For Auto Fan Speed, the fan speed increased based on dirtiness level:
c. Indoor Fan Control
• During any operation mode combines with Patrol operation, fan speed follows respective operation mode.
• During Patrol individual operation if e-ion starts, only Auto Fan Speed and no Powerful operation is allowed. Even if “Fan
Speed” button is pressed, no signal is sent to air conditioner, and no change on LCD display.
• During Patrol individual operation if e-ion stops, Indoor Fan stop operation.
Summary of Contents for CS-E12GKEW
Page 12: ...12 5 Dimensions 5 1 Indoor Unit ...
Page 13: ...13 5 2 Outdoor Unit ...
Page 15: ...15 7 Block Diagram ...
Page 16: ...16 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 17: ...17 8 2 Outdoor Unit ...
Page 18: ...18 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 19: ...19 9 2 Outdoor Unit ...
Page 20: ...20 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 21: ...21 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Panel 10 1 4 Patrol ...
Page 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 55: ...55 16 Technical Data 16 1 Operation Characteristics 16 1 1 CS E7GKEW CU E7GKE ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 59: ...59 16 1 2 CS E9GKEW CU E9GKE ...
Page 60: ...60 ...
Page 61: ...61 ...
Page 62: ...62 ...
Page 63: ...63 16 1 3 CS E12GKEW CU E12GKE ...
Page 64: ...64 ...
Page 65: ...65 ...
Page 66: ...66 ...