43
12.2.2.3. Freeze Prevention Control
1. When indoor heat exchanger temperature is lower than 0
°
C continuously for 6 minutes, compressor will stop operating.
2. Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 13
°
C.
3. At the same time, indoor fan speed in20 rpm compared to its normal operation.
4. If indoor heat exchanger temperature is higher than 13
°
C for 5 minutes, the fan speed will return to its normal operation.
12.2.3.
Protection Control For Heating Operation
12.2.3.1. Intake Air Temperature Control
Compressor will operate at Max freq. if either one of the below conditions occur:
1. When the indoor intake air temperature is 30
°
C or above.
12.2.3.2. Outdoor Air Temperature Control
The Max current value is regulated in accordance to the outdoor air temperature as shown in the below figures.
12.2.3.3. Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
Summary of Contents for CS-E12GKEW
Page 12: ...12 5 Dimensions 5 1 Indoor Unit ...
Page 13: ...13 5 2 Outdoor Unit ...
Page 15: ...15 7 Block Diagram ...
Page 16: ...16 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 17: ...17 8 2 Outdoor Unit ...
Page 18: ...18 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 19: ...19 9 2 Outdoor Unit ...
Page 20: ...20 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 21: ...21 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Panel 10 1 4 Patrol ...
Page 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 55: ...55 16 Technical Data 16 1 Operation Characteristics 16 1 1 CS E7GKEW CU E7GKE ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 59: ...59 16 1 2 CS E9GKEW CU E9GKE ...
Page 60: ...60 ...
Page 61: ...61 ...
Page 62: ...62 ...
Page 63: ...63 16 1 3 CS E12GKEW CU E12GKE ...
Page 64: ...64 ...
Page 65: ...65 ...
Page 66: ...66 ...