12.4. Operation Control
12.4.1. Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
12.4.2. 7 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
12.4.3. 60 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
• The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return
back to the outdoor unit.
12.4.4. Freeze Prevention Control
• If the temperature of the indoor heat exchanger falls below 2
°
C continuously for 4 minutes or more, the compressor turns off.
The fan speed setting remains the same.
• This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form
returning to the compressor.
• Compressor will restart again when the indoor heat exchanger temperature rises to 10
°
C (Recovery).
• Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
Summary of Contents for CS-C28GKF
Page 9: ...9 5 Dimensions 5 1 Indoor Unit ...
Page 10: ...10 5 2 Outdoor Unit ...
Page 11: ...11 6 Refrigeration Cycle Diagram ...
Page 12: ...12 7 Block Diagram ...
Page 13: ...13 8 Wiring Connection Diagram ...
Page 14: ...14 9 Electronic Circuit Diagram ...
Page 15: ...15 10 Printed Circuit Board 10 1 Main Printed Circuit Board ...
Page 16: ...16 ...
Page 17: ...17 10 2 Power Printed Circuit Board ...
Page 18: ...18 10 3 Indicator panel ...
Page 46: ...46 ...
Page 47: ...47 ...
Page 48: ...48 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures ...
Page 49: ...49 ...
Page 50: ...50 16 Technical Data 16 1 Thermostat Characteristics 1 Characteristics of thermostat ...
Page 51: ...51 16 2 Operation Characteristics ...
Page 52: ...52 ...
Page 54: ...54 ...