Connect The Piping to Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (located
at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.
Cutting and Flaring the Piping
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid
the metal powder entering the pipe.
3. Please make flare after inserting the flare nut onto the copper pipes.
11.2.3. AIR PURGING OF THE PIPINGS AND INDOOR UNIT
1) Checking a gas leakage
1. Remove the service-port cap from both 3-way valves.
2. Connect the Manifold gauge set to the service port of
Liquid side 3-way valve.
3. Connect the Charging Cylinder to the Manifold gauge set
and open the valve of the Cylinder.
4. Open the low pressure side valve of the Manifold gauge
for approx. 10 seconds and then close.
5. Check gas-leakage of the connecting portion of pipings
with the gas-leak detector.
<For the left pipings>
1) Measure the pressure.
2) Keep it for 5-10 minutes
•
Ensure if the pressure indicated on the gauge is as same as that of measured at first time.
2) Air purging
The air remaining in the Refrigeration cycle which contains
moisture may cause malfunction on the Compressor.
1. To purge the air, push the pin on the Gas side 3-way
valve for three seconds with a Hexagonal wrench and set
it free for one minute.
• Repeat this for three times.
2. To balance the refrigerant, close the low pressure side
valve on the Manifold gauge and release refrigerant from
the piping through service port until the gauge indicates
0.5 - 0.3 MPa.
3. Set both 3-way valves to open position with the
Hexagonal wrench for the unit operation.
Summary of Contents for CS-C28GKF
Page 9: ...9 5 Dimensions 5 1 Indoor Unit ...
Page 10: ...10 5 2 Outdoor Unit ...
Page 11: ...11 6 Refrigeration Cycle Diagram ...
Page 12: ...12 7 Block Diagram ...
Page 13: ...13 8 Wiring Connection Diagram ...
Page 14: ...14 9 Electronic Circuit Diagram ...
Page 15: ...15 10 Printed Circuit Board 10 1 Main Printed Circuit Board ...
Page 16: ...16 ...
Page 17: ...17 10 2 Power Printed Circuit Board ...
Page 18: ...18 10 3 Indicator panel ...
Page 46: ...46 ...
Page 47: ...47 ...
Page 48: ...48 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures ...
Page 49: ...49 ...
Page 50: ...50 16 Technical Data 16 1 Thermostat Characteristics 1 Characteristics of thermostat ...
Page 51: ...51 16 2 Operation Characteristics ...
Page 52: ...52 ...
Page 54: ...54 ...