48
14.1.1.
Relationship between the condition of the air conditioner and pressure and electric
current
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
14.1.2.
Diagnosis methods of a malfunction of a compressor
Cooling Mode
Condition of the air
conditioner
Low Pressure
High Pressure
Electric current during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or
Strainer
Short circuit in the indoor unit
Heat radiation deficiency of the
outdoor unit
Inefficient compression
Nature of fault
Symptom
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
• The discharge tube of the compressor becomes abnormally hot (normally 70 to 90
°
C).
• The difference between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor has a humming sound.
Summary of Contents for CS-C18GKD
Page 11: ...11 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS C18GK CS C24GK ...
Page 12: ...12 5 2 Outdoor Unit 5 2 1 CU C18GK 5 2 2 CU C24GK ...
Page 13: ...13 6 Refrigeration Cycle Diagram ...
Page 14: ...14 7 Block Diagram ...
Page 17: ...17 9 Electronic Circuit Diagram ...
Page 18: ...18 10 Printed Circuit Board 10 1 Indoor Unit TOP VIEW ...
Page 19: ...19 BOTTOM VIEW ...
Page 20: ...20 10 2 Indicator TOP VIEW BOTTOM VIEW ...
Page 50: ...50 ...
Page 51: ...51 ...
Page 52: ...52 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures ...
Page 53: ...53 ...
Page 54: ...54 16 Technical Data 16 1 Thermostat Characteristics Cooling Soft Dry ...
Page 55: ...55 16 2 Operation Characteristics 16 2 1 CS C18GK CU C18GK ...
Page 56: ...56 ...
Page 57: ...57 16 2 2 CS C24GK CU C24GK ...
Page 58: ...58 ...