26
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
11.2.4.
CONNECT THE CABLE TO THE OUTDOOR UNIT
1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3
×
2.5 mm
2
flexible
cord, type designation 245 IEC 57 or heavier cord.
3. Secure the cable onto the control board with the holder (clamper).
4. Attach the control board cover to the original position with the screw.
11.2.5.
Pipe Insulation
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E
FOAM with thickness 6mm or above.
CAUTION
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
• If the leak stops when the piping connections are tightened further, continue working from step 3.
• If the leak does not stop when the connections are retightened, repair the location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite.
Summary of Contents for CS-C18GKD
Page 11: ...11 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS C18GK CS C24GK ...
Page 12: ...12 5 2 Outdoor Unit 5 2 1 CU C18GK 5 2 2 CU C24GK ...
Page 13: ...13 6 Refrigeration Cycle Diagram ...
Page 14: ...14 7 Block Diagram ...
Page 17: ...17 9 Electronic Circuit Diagram ...
Page 18: ...18 10 Printed Circuit Board 10 1 Indoor Unit TOP VIEW ...
Page 19: ...19 BOTTOM VIEW ...
Page 20: ...20 10 2 Indicator TOP VIEW BOTTOM VIEW ...
Page 50: ...50 ...
Page 51: ...51 ...
Page 52: ...52 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures ...
Page 53: ...53 ...
Page 54: ...54 16 Technical Data 16 1 Thermostat Characteristics Cooling Soft Dry ...
Page 55: ...55 16 2 Operation Characteristics 16 2 1 CS C18GK CU C18GK ...
Page 56: ...56 ...
Page 57: ...57 16 2 2 CS C24GK CU C24GK ...
Page 58: ...58 ...