• Patrol Sensor Control
- First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness level is
monitored. The Air Dirtiness level is set to Clean, Patrol LED turns blue color.
- After that, Patrol sensor starts to record the resistance value at fixed interval. Higher resistance value indicates cleaner air.
- The air dirtiness level is monitored by comparing the current resistance value with maximum resistance value from time to
time to get the Air Dirtiness Value.
- There are 3 air dirtiness level, based on the Air Dirtiness Value:
- Air Dirtiness level 0: Clean - Patrol LED = blue color
- Air Dirtiness level 1: Moderate - Patrol LED = orange color
- Air Dirtiness level 2: Dirty - Patrol LED = red color
• Dirtiness level sensitivity adjustment.
It is possible to change the Patrol sensor sensitivity, where the Threshold value (G1 ~ G4) will be shifted accordingly:
1. Press and release “SET” button.
2. Press “Timer
” / “Timer
” button to select sensitivity.
(Air 1“Low Sensitivity” <
–
> Air 2 “Standard” (Default) <
–
> Air 3 “High Sensitivity”)
3. Confirm setting by pressing “Timer Set” button. LCD returned to original display after 2 seconds.
4. LCD returned to original display if remote control does not operate for 30 seconds.
• e-ion Control
- e-ion operation starts condition
- When dirtiness at level 2 (Patrol LED turns red).
- 2 minutes after stabilization time (Patrol LED turns red).
- 4 hours at level 0 (Patrol LED turns red).
- e-ion operation time
- If dirtiness level improves from level 2 to level 1 (Patrol LED from red to orange), the unit carries out level change after 60
seconds.
- When dirtiness level returns to level 0 (Patrol LED turns blue) continuously for 11 minutes or more, e-ion operation stops.
• Dirtiness Level and fan speed
- When e-ion operation starts, the fan speed increases based on dirtiness level:
- Indoor Fan Control
- During any operation mode combines with Patrol operation, fan speed follows respective operation mode.
- During Patrol individual operation if e-ion starts, only Auto Fan Speed and no Powerful operation is allowed. Even if “Fan
Speed” button is pressed, no signal is sent to air conditioner, and no change on LCD display.
- During Patrol individual operation if e-ion stops, Indoor Fan stop operation.
Summary of Contents for CS-C12HKF
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS C12HK ...
Page 10: ...10 5 2 Outdoor Unit 5 2 1 CU C12HK ...
Page 11: ...11 6 Refrigeration Cycle Diagram ...
Page 12: ...12 7 Block Diagram ...
Page 14: ...14 9 Electronic Circuit Diagram ...
Page 15: ...15 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board TOP VIEW ...
Page 16: ...16 BOTTOM VIEW ...
Page 17: ...17 10 1 2 Power Printed Circuit Board TOP VIEW BOTTOM VIEW ...
Page 18: ...18 10 1 3 Indicator TOP VIEW BOTTOM VIEW ...
Page 46: ...46 ...
Page 47: ...47 16 1 3 To remove discharge grille 16 1 4 To remove control board ...
Page 48: ...48 16 1 5 To remove cross flow fan and indoor fan motor ...
Page 49: ...49 ...
Page 50: ...50 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...
Page 51: ...51 17 2 Operation Characteristics 17 2 1 CS C12HK CU C12HK ...
Page 52: ...52 ...
Page 54: ...54 ...