117
Aquarea air / water heat pump – design handbook 07 / 2014
Appendix
Heating capacity in relation to supply water and outside temperature
Aquarea LT
Outside temperature
Supply water temperature
Models
30
35
40
45
50
55
3 kW (single phase)
WH-SDF03E3E5
WH-SDC03E3E5
-15
3 .2
3 .2
3 .1
3 .0
2 .8
2 .75
-7
3 .2
3 .2
3 .2
3 .2
3 .2
3 .2
2
3 .2
3 .2
3 .2
3 .2
3 .2
3 .2
7
3 .2
3 .2
3 .2
3 .2
3 .2
3 .2
25
3 .2
3 .2
3 .2
3 .2
3 .2
3 .2
30
35
40
45
50
55
5 kW (single phase)
WH-SDF05E3E5
WH-SDC05E3E5
-15
4 .2
4 .2
3 .8
3 .4
3 .2
3 .0
-7
4 .2
4 .2
4 .0
3 .8
3 .7
3 .55
2
4 .2
4 .2
4 .2
4 .2
4 .15
4 .1
7
5 .0
5 .0
5 .0
5 .0
5 .0
5 .0
25
5 .0
5 .0
5 .0
5 .0
5 .0
5 .0
30
35
40
45
50
55
7 kW (single phase)
WH-SDC07F3E5¹
WH-SDF07C3E5
WH-SDC07C3E5
(Phase-out models)
-15
4 .6
4 .3
4 .6
4 .6
4 .6
4 .5
-7
5 .2
5 .8
5 .1
5 .0
4 .9
4 .5
2
6 .7
6 .6
6 .6
6 .7
6 .3
6 .0
7
7 .0
7 .0
7 .0
7 .4
6 .9
6 .8
25
7 .0
7 .0
6 .4
6 .1
5 .9
5 .7
30
35
40
45
50
55
9 kW (single phase)
WH-SDC09F3E5¹
WH-SDF09C3E5
WH-SDC09C3E5
(Phase-out models)
-15
6 .0
5 .9
5 .5
5 .4
5 .2
5 .0
-7
6 .1
6 .6
5 .9
5 .8
5 .8
5 .6
2
6 .8
7 .0
6 .7
6 .7
6 .3
6 .0
7
9 .0
8 .8
9 .0
9 .0
9 .0
9 .3
25
9 .0
9 .0
8 .4
8 .0
7 .8
7 .5
30
35
40
45
50
55
9 kW (three phase)
WH-SDC09F3E8¹
WH-SDF09C3E8
WH-SDC09C3E8
(Phase-out models)
-15
8 .7
8 .0
8 .0
7 .6
7 .2
6 .7
-7
9 .4
9 .5
8 .9
8 .7
8 .3
7 .5
2
9 .3
8 .8
9 .0
9 .0
8 .9
8 .8
7
9 .0
8 .5
9 .0
8 .5
9 .0
8 .1
25
9 .0
9 .0
8 .7
8 .5
8 .3
8 .1
30
35
40
45
50
55
12 kW (single phase)
WH-SDC12F6E5¹
WH-SDF12C6E5
WH-SDC12C6E5
(Phase-out models)
-15
9 .3
9 .0
8 .5
8 .1
7 .5
7 .0
-7
10 .4
10 .7
9 .6
9 .2
8 .7
8 .6
2
11 .8
12 .0
11 .0
10 .9
9 .8
9 .1
7
12 .0
11 .9
12 .0
11 .8
12 .0
11 .6
25
12 .0
12 .0
11 .8
11 .7
11 .5
11 .4
30
35
40
45
50
55
14 kW (single phase)
WH-SDC14F6E5¹
WH-SDF14C6E5
WH-SDC14C6E5
(Phase-out models)
-15
9 .9
9 .7
9 .0
8 .6
7 .9
7 .3
-7
11 .1
11 .6
10 .2
9 .8
9 .1
8 .8
2
12 .9
12 .7
11 .9
11 .8
10 .4
9 .5
7
14 .0
13 .9
14 .0
14 .2
13 .6
12 .8
25
14 .0
14 .0
14 .0
14 .0
14 .0
14 .0
30
35
40
45
50
55
16 kW (single phase)
WH-SDC16F6E5¹
WH-SDF16C6E5
WH-SDC16C6E5
(Phase-out models)
-15
10 .6
10 .2
10 .0
9 .7
8 .8
7 .9
-7
11 .9
12 .3
10 .8
10 .3
9 .6
9 .4
2
13 .5
13 .4
12 .4
12 .1
10 .8
9 .8
7
16 .0
16 .0
16 .0
15 .8
15 .2
14 .2
25
16 .0
16 .0
16 .0
16 .0
16 .0
15 .9
Heating capacity [kW] of individual models of the
bi-bloc system
for different supply water and outside temperatures [°C].
¹
Preliminary specifications