Voltage input range: +1 to +5 V
Input range: +1 to +5 V
Analog input
value
(V)
Digital conversion
value
(K)
+5
+25,600
+4
+19,200
+3
+12,800
+2
+6,400
+1
0
0
0
When exceeding the rated range
Analog input
value
Converted value
+5 V or more
+25,600
+1 V or less
0
■
Current Input range: 0 to +20 mA
Input range: 0 to +20 mA
Analog input
value
(mA)
Digital conversion
value
(K)
+20
+32,000
+16
+25,600
+12
+19,200
+8
+12,800
+4
+6,400
0
0
When exceeding the rated range
Analog input
value
Converted value
+20 mA or more
+32,000
0 mA or less
0