Voltage input range: 0 to +10 V
Input range: 0 to +10 V
Analog input
value
(V)
Digital conversion
value
(K)
+10
+32,000
+8
+25,600
+6
+19,200
+4
+12,800
+2
+6,400
0
0
When exceeding the rated range
Analog input
value
Converted value
+10 V or more
+32,000
0 V or less
0
■
Voltage input range: 0 to +5 V
Input range: 0 to +5 V
Analog input
value
(V)
Digital conversion
value
(K)
+5
+32,000
+4
+25,600
+3
+19,200
+2
+12,800
+1
+6,400
0
0
When exceeding the rated range
Analog input
value
Converted value
+5 V or more
+32,000
0 V or less
0