8-22
Specifications
Error codes 80 to 106
Code
Name
Operation
Error contents and steps to take
80
Unit alarm occurrence
Select
(Default stop)
An alarm has occurred in an attached unit. Check the
status of the unit in the slot number saved in the
system data register SD1.
81
Unit error occurrence
Select
(Default stop)
An error has occurred in an attached unit. Check the
status of the unit in the slot number saved in the
system data register SD2. Verify the configuration
settings.
82
Unit verification error
detection
Select
(Default stop)
Unit wiring condition has changed compared to that at
the time of power-up.
Check the status of the unit in the slot number saved
in the system data register SD4.
83
Registered unit number
inconsistency
Select
(Default stop)
The number of units differs from that registered in the
I/O map. Check the I/O map and the attachment
status.
84
Unit initial completed
Waiting timeout
Select
(Default stop)
An error has occurred during the unit initial operation.
Check the unit status.
85
Unit configuration data
inconsistency with
applicable unit
Select
(Default stop)
The unit's configuration data is not consistent with the
applicable unit. Check the I/O map and the
configuration data.
86 Operation
error
Select
(Default stop)
An operation error has occurred. Reasons for an
operation error vary by instruction. Refer to the
Instruction Manual, etc. and correct the appropriate
reasons. PB and address where an operation error
has occurred are saved in the system data registers
SD7 to SD12.
100
Bus current error
Select
(Default continue)
A bus error is probable. Please contact your dealer.
104
Service power supply
current error
Select
(Default continue)
An error has been detected in the GT power supply
terminal part. Check if it is correctly connected.
105
CPU temperature error 1
Select
(Default continue)
106
CPU temperature error 2
Select
(Default continue)
A temperature rise has been detected in hardware. In
general, select "Continue".
(Note 1) For errors where "Select" is indicated in the 'Operation' column, either "Stop" or "Continue" can be selected
in the configuration menu.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for AFP7PSA1
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 9: ...1 Overview Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 47: ...5 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 62: ...5 16 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 77: ...8 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...