8.2
Power Supply Unit Specifications
8-25
8.2.2 Performance Specifications
Items
Description
Rated input voltage
100 to 240V AC
Input voltage amplitude range
85 to 264V AC
Rated frequency
50 / 60 Hz
Frequency range
47 to 63 Hz
Phases
Single-phase
Input current
AFP7PSA1: 0.75A
AFP7PSA2: 1.25A
Inrush current
40 A (0-P) or less; Cold start
Leakage current
0.75 mA or less between AC input and protective earth terminals
Input
Momentary power drop time
10 ms or more
Rated output current (Note 1)
AFP7PSA1: 24V DC, 1A
AFP7PSA2: 24V DC, 1.8A
Output
Overcurrent protection (Note 2)
On
Guaranteed lifetime
27,000 hours (+55
C)
Terminal screw
Built-in (Replacement is not available)
(Note 1) Use the unit within the rated output current.
(Note 2) Oscillation is stopped during protected operation.
To recover, turn off the input and then on again. Wait at least 180 seconds before turning the input on again.
8.2.3 Alarm Output Specifications
Items
Description
Contact capacity
1A 30V DC
Alarm contact operations
Contact OFF at CPU alarm occurrence
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for AFP7PSA1
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 9: ...1 Overview Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 47: ...5 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 62: ...5 16 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 77: ...8 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...