6-2
Troubleshooting
6.1 Self-Diagnosis Function
6.1.1 CPU Unit's Operation Monitor LED
The CPU unit has a self-diagnostic function which identifies errors and stops operation if
necessary. Indications concerning self-diagnosis are as follows.
LED indications concerning self-diagnosis errors
LED indications on the CPU unit
RUN
Green
PROG
Green
ERROR
Red
ALARM
Red
Description
Operation
status
●
○
○
○
Normal operation
Operation
○
●
○
○
PROG. mode
Stop
Normal
operation
▲
○
○
○
Forcing input/output in the
RUN mode
Operation
●
○
▲
○
When a self-diagnostic error
occurs (Operation)
Operation
○
●
▲
○
When a self-diagnostic error
occurs (Stop)
Stop
○
●
●
System watchdog timer has
been activated
Stop
Error
○
▲
○
Waiting for connection of the
PHLS slave
Stop
(Note)
●
: ON,
▲
: Flashing,
○
: OFF, -: Varies (ON or OFF)
6.1.2 Operation at the Time of Error
Normally, when an error occurs, the operation stops.
Configuration menu of FPWIN GR7
Operation mode of the CPU unit at the time of error can be set (Continue or Stop) in the "FP7
Configuration" menu of the tool software FPWIN GR7.
CPU configuration
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for AFP7PSA1
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 9: ...1 Overview Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 47: ...5 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 62: ...5 16 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 77: ...8 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...