3.5
Confirmation of Load Factor Calculation
3-21
3.5 Confirmation of Load Factor Calculation
3.5.1 Load Factor Calculation
The load factor is the calculated ratio of the number of actually used packets to the maximum
number of packets which the FP0H can send/receive in one second by cyclic communication.
•
Packets other than by cyclic communication or unnecessary received packets are not
considered for calculating the load factor.
•
Reserved nodes are not included in the calculation of load factor.
3.5.2 Displaying Load Factor Calculation
The following procedure is explained on the assumption that the EtherNet/IP setting screen
has been activated.
PROCEDURE
1. Select the uppermost "FP0H C32ET/EP(192.168.1.6) Usable Connect...) from
Scan List.
The "Calculate Load Factor" window appears.
2. Confirm each load factor of the whole unit, I/O map and scan list.
Load factors for each setting of I/O map and scan list are calculated separately.
•
The load factors of FP0H and each target should be 100% or less.