Setting Procedure
3-6
3.2.3 EtherNet/IP Basic Configuration
Make the EtherNet/IP basic configuration. The following procedure is explained on the
assumption that the EtherNet/IP setting screen has been activated.
PROCEDURE
1. Select "Setting" > "EtherNet/IP Basic Configuration" from the menu bar.
The EtherNet/IP Basic Configuration dialog box appears.
2. Change the settings of "Auto Allocation" and "RUN/IDLE bit operation of
cyclic communication" as necessary.
In this example, "Auto Allocation = No", and "RUN/IDLE bit operation of cyclic
communication = Normal".
3. Press the [OK] button.
KEY POINTS
•
When allocating devices manually, set "Auto Allocation" to "No".
•
For performing operation check, set "RUN/IDLE bit operation of cyclic
communication" to "Limited". When selecting "Normal", the RUN/IDLE bit of
the FP0H does not turn "ON" unless the communications with all the targets
registered in the scan list are established.