Fire alarm solutions

technical description

ENCLOSED HEAT 

DETECTOR

www.panasonic-fire-security.com     

Summary of Contents for 6295

Page 1: ...6295 6298 Fire alarm solutions technical description ENCLOSED HEAT DETECTOR www panasonic fire security com...

Page 2: ...LATCHING 5 3 1 2 EXTERNAL LED 6 3 2 CONNECTION BOX 6 3 3 ZONE LINE INPUT 6 4 MOUNTING 7 5 INSTALLATION AND WIRING 8 5 1 COMMON INSTALLATION 6295 6298 8 5 2 INTRINSICALLY SAFE INSTALLATION 6295 6296 9...

Page 3: ...FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 3 1 INTRODUCTION This document describes the enclosed heat detectors type number 6295 6298 The document contains information about the product and instructio...

Page 4: ...6295 6298 ENCLOSED HEAT DETECTOR FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 4 2 ABBREVIATIONS CIE Control and indicating equipment control unit LED Light Emitting Diode...

Page 5: ...onnection box 3 1 DETECTOR The sensing element is a heat pick up shield and a bimetal switch The detectors will give an alarm within a response temperature range in accordance with EN54 5 see table be...

Page 6: ...en the detector is used as intrinsically safe detector in hazardous Ex areas see 5 2 INTRINSICALLY SAFE INSTALLATION 6295 6296 on page 9 3 2 CONNECTION BOX The connection box is prepared for required...

Page 7: ...he cables in the compression glands If the outer cable diameter is 6 mm insert the enclosed rubber tube before installation of the cable If the outer cable diameter is 6 mm do not use the enclosed rub...

Page 8: ...TIONS TECHNICAL DESCRIPTION 8 5 INSTALLATION AND WIRING 5 1 COMMON INSTALLATION 6295 6298 Screen wire termination is not provided 6295 6298 6295 6298 End of line device Wire size Min 0 6 mm 0 3 mm Wir...

Page 9: ...le Hazardous Ex area Zone line Channel Alternative A Alternative B Zone Zone 4461 2822 Exp Board 4580 EX zone line input Galvanic Isolator Barrier unit A B Ui 30 V Ii 40 mA Ci 3 nF Li 0 H Uo Ui 30V Io...

Page 10: ...to resistance ratio F mH or H ohm IIC 0 13 4 2 55 Maximum total cable resistance is 40 ohm The zone line cable in the Ex area the zone line cable in the safe area should be 40 ohm Please use appropri...

Page 11: ...ALARM SOLUTIONS TECHNICAL DESCRIPTION 11 6 TEST MODE For information about how to set a zone in test mode see Planning Instructions or Operating Instructions It is possible to use test equipment for...

Page 12: ...ximum 40 mA Alarm resistance 400 Internal capacitance Internal inductance 3 nF 0 nF Short circuit isolator No Internal battery No Material FR ABS and polycarbonate Ambient temperature Operating Storag...

Page 13: ...ximum 40 mA Alarm resistance 400 Internal capacitance Internal inductance 3 nF 0 nF Short circuit isolator No Internal battery No Material FR ABS and polycarbonate Ambient temperature Operating Storag...

Page 14: ...scent Active 0 mA 35 mA Current limitation required when active Must be minimum 6 and maximum 40 mA Alarm resistance 400 Short circuit isolator No Internal battery No Material FR ABS and polycarbonate...

Page 15: ...cent Active 0 mA 25 mA Current limitation required when active Must be minimum 6 and maximum 30 mA Alarm resistance 680 Short circuit isolator No Internal battery No Material FR ABS and polycarbonate...

Page 16: ...61000 6 3 Emission EN50130 4 Immunity Self declaration RoHS EN IEC 63000 Self declaration ATEX EN IEC 60079 0 EN 60079 11 Self declaration Applicable directive Approval Applicable standards Notified b...

Page 17: ...RIPTION 6295 6298 DOCUMENT NUMBER MEW01946 EN DATE OF ISSUE 2016 01 11 REV 4 DATE OF REVISION 2022 09 13 Panasonic Fire Security Europe AB Jungmansgatan 12 SE 211 11 Malm SE Tel 46 0 40 697 70 00 www...