6295-6298 ENCLOSED HEAT DETECTOR
- FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION
10
Channel
: Maximum 5 units on the Zone line (Channel), Cable FKAR-PG 2x0.5 mm², blue
(with aluminum polyester foil tinned copper drain wire 1 mm² is normally not used/connected)
Zone
: EKKR / ELQRB 2x0.6 mm (0.3 mm²) Connection of alarm points is not allowed on this line.
The interconnecting cable should have the following maximum parameters:
Group
Capacitance Inductance Inductance to resistance ratio
µF
mH or µH / ohm
IIC
0.13
4.2
55
Maximum total cable resistance is 40 ohm. The zone line cable in the Ex area + the zone line cable in the
safe area should be ≤ 40 ohm.
** Please use appropriate galvanic isolator / barrier unit when using is as ATEX ic detector.
It must be compliant with EN60079-11:2012:
Uo<=Ui (=30V)
Io<=Ii (=40mA)
Co > = Ci x 5 (15nF)
Lo >= Li (0 H)
5.2.1.
RATING LABEL
Serial Number of type 6295/6296 is indicated on the rating label.
5.2.2.
CABLE GLAND
Specification for included cable gland: PA6, Marking: “bimed” “PF1/2”
Wire size min-max, circular cable : Ø 4.0 - 8.0 mm
Running number (1-99999)
Production month
Production year
SILVER GROUND
PRINTED BLACK