6295-6298 ENCLOSED HEAT DETECTOR
- FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION
15
10. TECHNICAL DATA 6298
All current consumptions are valid by nominal voltage and by 25 °C.
Voltage:
Allowed
Normal
12 – 30 V DC
24V DC (Zone line voltage)
Current:
Quiescent
Active
0 mA
25 mA
Current limitation required when active
Must be minimum 6 and maximum 30 mA
Alarm resistance
680 Ω
Short circuit isolator
No
Internal battery
No
Material
FR ABS and polycarbonate
Ambient temperature:
Operating
Storage
-40 to +110 °C
-45 to +70 °C
Static response temperature
117 °C
Ambient humidity
Maximum 95 % RH (Non condensing)
Ingress protection rating
IP67
Size:
Ø x H
100 x 75 mm
Weight:
82 g
Colour
Grey (N8, Munsell colour code)