![Panasonic 6295 Manual Download Page 13](http://html1.mh-extra.com/html/panasonic/6295/6295_manual_3799185013.webp)
6295-6298 ENCLOSED HEAT DETECTOR
- FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION
13
8. TECHNICAL DATA 6296
All current consumptions are valid by nominal voltage and by 25 °C.
Voltage:
Allowed
Normal
12 – 30 V DC
24V DC (Zone line voltage)
Current:
Quiescent
Active
0 mA
35 mA
Current limitation required when active
Must be minimum 6 and maximum 40 mA
Alarm resistance
400 Ω
Internal capacitance
Internal inductance
3 nF
0 nF
Short circuit isolator
No
Internal battery
No
Material
FR ABS and polycarbonate
Ambient temperature:
Operating
Storage
-40 to +65 °C
-45 to +70 °C
Static response temperature
72 °C
Ambient humidity
Maximum 95 % RH (Non condensing)
Ingress protection rating
IP67
ATEX classification
II 3 G Ex ic IIC T5 Gc X, II 3 D Ex ic IIIC T100°C Dc X
-40°C ≤ Ta ≤ 65°C / EN IEC 60079-0 :2018,
EN 60079-11 :2012
Size:
Ø x H
100 x 75 mm
Weight:
82 g
Colour