Technical Manual
5054 Rev 0
For Firmware V2.0.x
16
5.9 Network Settings
Network settings will show basic system information e.g. device name, IP address, etc.
5.10 Selective Alarm Presentation
Normally all fire alarms will be presented in the FDCIE and 5054. It is possible to select which
alarms may be presented in the display unit. For example, if there are many buildings in a
system, the units in one specific building can present alarms activated within this building
only.
The following operands are available (FT128 is always CU 00):
•
Control unit (
CU
)
•
Consecutive control units (
CU1, CU2
)
•
Zone (zone)
•
Consecutive zone (
zone1, zone2
)
•
Zone – address (
zone, addr
)
•
Consecutive zone – address (
zone1, addr1, zone2, addr2
)
Up to 50 operands can be selected for a display unit.
Example
: Control unit (
00
), Consecutive zones (
100, 500
), Zone – address (
900, 01
). In this
unit, the alarms that originated from the FDCIE no. 00, from the zone 100-500, or
from the alarm point 900-01 will be presented.
Default programming in FT1020G3 system is Control units (00, 29). All alarms from all
FDCIE’s will be presented in all display units.
Default programming in FT128 system is Control units (00, 00). All alarms will be presented
in all display units.
The programming is performed via EBLWin.