Technical Manual
5054 Rev 0
For Firmware V2.0.x
14
5 Service Menu
A new display unit has no unit type, address, or language selected, it is factory set to "Not
selected". When the display unit is powered for the first time it will automatically display the
service menu as shown below.
For a display unit in operation, the service menu can be opened via the jumper "J4" in the
unit. Remove the two screws (Torx T10) at the bottom of the display unit to open the unit.
Note
: The screws are mounted at a 45⁰ angle
, Torx driver must be used to remove mounting
screws.
The service menu can also be opened via menu “Activate address setting mode for DU” in
the FDCIE, see the operation manual for the FDCIE.
5.1 Unit Type
When 5054 is connected to FT128 or FT1020G3, the unit type can be changed to one of the
following:
•
External presentation unit
•
Alert annunciation unit
•
Fire brigade panel (
not used in Australia, not conforming to AS4428.3
)
Select the required unit type and press to save the settings.
5.2 Compatibility and EBLWin Configuration:
Set the display unit type according to the table below:
System
FT1020G3 Software
Fire brigade panel
1)
V
≥
2.8.x
Alert annunciation unit
2)
V
≥
2.8.x
External presentation unit
3)
V
≥
2.8.x