Technical Manual 

5054

 

Rev 0  

 

 

 

 

 

 

 

 

D

ISPLAY 

U

NIT 

5054 

 

Firmware V2 

 

 

 

 

 

 

 

 

 

 

 

 

 

MA446

 

 

 

 

 

 

 

 

 

May 2021

 

 

Summary of Contents for 5054

Page 1: ...Technical Manual 5054 Rev 0 DISPLAY UNIT 5054 Firmware V2 MA446 May 2021 ...

Page 2: ...This page has deliberately been left blank ...

Page 3: ... 1 Fire Alarm 9 3 1 1 Fire Alarm without Alert Annunciation normal alarm 9 3 1 2 Fire Alarm with Alert Annunciation 10 3 2 Alert Annunciation Function 11 3 3 Buzzer 11 3 4 Quiet Alarm 12 3 5 Operation 12 3 6 Buttons 12 4 EXTERNAL FIRE BRIGADE PANEL 13 5 SERVICE MENU 14 5 1 Unit Type 14 5 2 Compatibility and EBLWin Configuration 14 5 3 Unit Address 15 5 4 Language Area 15 5 5 Display Brightness 15 ...

Page 4: ...11 INSTALLATION AND WIRING 29 12 RESTART 30 13 COMMISSIONING 31 14 SPECIFICATIONS 32 15 GUARANTEE 33 16 REVISION HISTORY 34 Table of Figures Figure 1 Dimensions of 5054 Display Unit 3 Figure 2 5054 Display configured as an External Presentation Unit 7 Figure 3 5054 configured as an Alert Annunciation Unit 9 Figure 4 Fire brigade option not conforming to AS4428 3 13 Figure 5 Display unit property w...

Page 5: ...t 1736 style When the alert annunciation function is required in the FDCIE 5054 presents fire alarm messages and provide buttons to acknowledge and reset the alert annunciation alarms External fire brigade panel Currently not conforming to AS4428 3 as the disable button is not supported and the red boarder is not shown i e cannot be used as fire brigade panel in Australia The display unit meets th...

Page 6: ...elden 7703NH 1pr 1 pair of Communication LonWorks 1200 m Note Maximum cable length for communications is 1200 m irrespective of the cable type Brooks recommend to use higher gage shielded cables for communications e g 0 7 mm or 1 0 mm 1 2 3 Separate power supply cable Power Cable Type Distance to unit Belden 5120UL 14 1 pair for power supply Fire Alarm 14 1600 m Belden 5220UL 16 1 pair for power s...

Page 7: ...isplay is a coloured touch screen The screen brightness and volume can be adjusted see section 5 5 Display Brightness page 15 The touch screen goes to sleep mode after 2 minutes Specifications Display size 10 1 TFT Screen LCD type Capacitive display Resolution 1024x600 RGB ...

Page 8: ...nnection 7 Number of zones in alarm Note The above picture is only for illustration it cannot be used as a fire brigade panel Extinguishing Outputs for extinguishing equipment are activated Ventilation Outputs for smoke control ventilation system are activated Fire brigade tx Output for fire brigade tx routing equipment is activated Note The symbols are greyed out when the event is not active ...

Page 9: ... Upon receiving a fire signal the fire alarm indicator will flash 0 4 0 4 s for a real fire alarm it will not flash for pre warning or co incidence and depending on the type of alarm the following indicators may be illuminating The button Silence buzzer is available to silence the display unit buzzer If two or more alarms are activated in the system the button Alarms queued will be shown and you c...

Page 10: ...ay unit 2 5 Fault Fault in the system will be displayed as General faults in system on the display When the fault symbol is activated the display back light is turned on for two minutes The back light will remain turned on with 10 screen brightness as long as faults exist in the system The buzzer will sound steady as long as the fault is not acknowledged in the system A fire alarm has higher prior...

Page 11: ...t condition no buttons will be shown 3 1 Fire Alarm 3 1 1 Fire Alarm without Alert Annunciation normal alarm When a normal fire alarm is activated fire alarms and heavy smoke heat alarms will be presented on the display The fire alarm indicator will flash 0 4 0 4S and the Fire brigade alerted symbol is activated If two or more alarms activated in the system the button Alarms queued will be shown a...

Page 12: ...wledged the investigation time starts The fire alarm indicator will stop flashing and the button Reset will be available to reset the alert annunciation alarm If the alarms are not reset within the investigation time the Fire brigade alerted symbol will be activated If two or more alarms exist in the system the button Alarms queued will be shown and the user can scroll amongst the alarms When all ...

Page 13: ...on alarm is allowed but up to four zones can be programmed Acknowledgement and reset of an alert annunciation alarm can be performed from the display unit A programmable output for indication and programmable inputs for acknowledge or reset alert annunciation alarm can also be used Acknowledge time and investigation time are set in system properties in EBLWin The acknowledgement time can be set to...

Page 14: ...ton Acknowledge can be used to acknowledge the alert annunciation alarms Reset is Visible when a fire alarm is activated The button Reset can be used to reset the fire alarms in the system This button is password protected see section 5 7 page 15 Alarms Queued is Visible when two or more fire alarms exist in the system In case of multiple alarms the button Alarms queued will be visible and the use...

Page 15: ...rigade option not conforming to AS4428 3 1 Fire alarm indicator 2 Extinguishing symbol 3 Ventilation symbol 4 Fire brigade tx symbol 5 Silence buzzer 6 Silence alarm devices 7 Reset 8 Alarms queued Note The current fire brigade panel cannot be used in Australia It s not conforming to the AS4428 3 ...

Page 16: ...Torx driver must be used to remove mounting screws The service menu can also be opened via menu Activate address setting mode for DU in the FDCIE see the operation manual for the FDCIE 5 1 Unit Type When 5054 is connected to FT128 or FT1020G3 the unit type can be changed to one of the following External presentation unit Alert annunciation unit Fire brigade panel not used in Australia not conformi...

Page 17: ...ge English and press to save the settings 5 5 Display Brightness The default screen brightness is set to 50 The brightness may need to be changed due to the lighting conditions Change the brightness level with the arrow buttons and press to save the settings 5 6 Buzzer Sound Volume You can set the volume for the buzzer and the sound for when a button is pressed Change the volume with the arrow but...

Page 18: ...28 is always CU 00 Control unit CU Consecutive control units CU1 CU2 Zone zone Consecutive zone zone1 zone2 Zone address zone addr Consecutive zone address zone1 addr1 zone2 addr2 Up to 50 operands can be selected for a display unit Example Control unit 00 Consecutive zones 100 500 Zone address 900 01 In this unit the alarms that originated from the FDCIE no 00 from the zone 100 500 or from the al...

Page 19: ...xt messages for all or selected alarm points zones can also be stored in each display unit These alarm texts will be shown instead of the alarm texts sent out from the FDCIE Up to 617 unique user definable texts can be programmed in the memory for each unit If a word or a whole sentence is reused in another alarm text more than 617 user definable texts can be added to the memory The priority order...

Page 20: ...5 Ensure that the file system software version matches the firmware version File system damaged Waiting for command over USB Something went wrong during the download or the wrong file was downloaded Try to download again see section 9 4 File System Download page 25 Ensure that the file system version matches the firmware version File system version incompatible Waiting for command over USB Somethi...

Page 21: ...utton or the information button to open a pop up window 3 Press anywhere on the window to close A new fire alarm has higher priority and will be displayed instead of the camera window or the information window When all fire alarms in the system are reset the pop up window will be closed 8 1 EBL Graphics An EBL Graphics project needs to be created to connect the IP cameras to the alarm points 1 Cre...

Page 22: ... 7 Click Save and close 8 Open the Windows Control Panel Administrator Tool Service 9 Select EBL Service and click Start The IP address of the PC with EBL Service installed also need to be set in EBLWin 10 Open the Display unit 5054 properties window in EBLWin as shown in Figure 5 below 11 Enter the Server IP address and Server port 12 If a static IP number not DHCP shall be used the following dat...

Page 23: ...cal Manual 5054 Rev 0 For Firmware V2 0 x 21 Figure 5 Display unit property window in EBLWin Note The bottom section of the 5054 properties window shown in Figure 5 above is available only in software V2 0 x ...

Page 24: ...nits connected to the same RS485 bus must have the same firmware version and file system version e g V2 0 x and V2 0 x respectively X indicates only a small correction and is not required to be the same It is highly recommended to have the same versions in all the 5054 units in the system 9 2 Display unit 5054 Driver A driver is required to download the firmware and the file system software into y...

Page 25: ...f the firmware to the unit as shown in the following procedures 1 Connect the PC to the display unit via a USB and start EBLWin 2 In EBLWin click Tools Download software to open the EBL Firmware Manager the following window displays 3 Select the Display unit 5054 tab 4 Browse to the firmware file location in your PC to be downloaded DU5054_x x x_FW dfu You must select the correct file extension No...

Page 26: ...download a new firmware A Display unit driver in section 9 2 Display unit 5054 Driver page 22 is needed when the unit is in boot mode Make sure you have the driver installed on your computer before you open EBL Firmware Manager If the driver is missing when downloading firmware the following fault message will be shown The latest Display unit driver can be downloaded from the homepage 1 Force the ...

Page 27: ...ile system location in your PC to be downloaded DU5054_x x x_FS bin You must select the correct file extension Note When you browse to select the FS bin file ensure to select the correct extension as shown below 5 Select COM Port as per section 9 3 above 6 Click Start to download the file system the following window will be shown 7 When the download is completed the pop up dialog Download complete...

Page 28: ...2 Disconnect the loudspeaker cable see left arrow below 3 Remove terminal block J5 from the PCB as shown below right arrow 4 Cut out the required number of knockouts into the top bottom or rear 5 Enter the cables into the box Note The cable length should be as long as possible when entering from top Move the ground bar plate to the lower position when entering from top 6 Mount the box on the wall ...

Page 29: ...e secured connection do not let the sprawl outside the cable fixing clamp Note The ground bar plate is reversible to fit all cable thicknesses 10 Connect the ground cable to the ground bar plate 11 Reconnect the terminal block J5 to the P C B 12 Reconnect the loudspeaker 13 Assemble the front of the display unit with the two screws Be careful not to pinch any cables Note The screws are mounted at ...

Page 30: ...Technical Manual 5054 Rev 0 For Firmware V2 0 x 28 10 1 Drill Measurement ...

Page 31: ...in last unit J7 Used to connect the built in end of line resistor secondary terminal for redundant connection Note J3 or J7 must only be shunted if the unit is the last unit on the RS485 bus J5 Primary terminal block to connect to FDCIE or next unit J6 Secondary terminal block is used for redundant connection of communication and power supply when this is supported by the FDCIE new 5012 in G3 Note...

Page 32: ...llowing message will display Memory fault in program area n n 1 or 2 The display unit will not work and a fault message will be shown in the FDCIE FT1020G3 FAULT No reply display unit xx control unit xx FT128 FAULT No reply EPU x If an SSD memory fault in 5054 or no SSD downloaded the display unit will still work since the alarm texts will be sent out from the FDCIE A fault message will be shown i...

Page 33: ...ype Address and Language 1 Select Service menu Unit Address Language 2 Select Unit type and choose one of the unit types Press 3 Select Unit Address and set the address with the arrow buttons Press 4 Select Language and then choose English from the list Press 5 Return to the Service menu and press the Save Restart Device button The unit will restart Programming in EBLWin and Downloading SSD 1 Conn...

Page 34: ...t temperature Operating Storage 5 to 40 C 30 to 80 C Ambient humidity Maximum 93 RH Non condensing Ingress protection rating IP 30 Size H x W x D 169 x 264 x 56 mm Weight 1400 g Colour Light grey NCS S 1500 N Note the current consumption shown in the table above is the maximum allowed current depending on the supply voltage Approvals Applicable directive Approvals Applicable standards Notified bod...

Page 35: ...wsoever caused careless handling or where repairs have been made or attempted by others No other guarantees written or verbal are authorised to be made on behalf of Brooks All other conditions and warranties whether expressed or implied are to the extent permitted by law hereby excluded As Brooks has no control over the system s design installation to the relevant Australian Standard or maintenanc...

Page 36: ...Technical Manual 5054 Rev 0 For Firmware V2 0 x 34 16 Revision history Issue Date Description Written By Checked By 1 7 5 2021 First revision of firmware V2 03 Manual A S AS HN ...

Page 37: ...ria Crescent Abbotsford VIC 3067 Ph 03 9879 5294 SA P O Box 101 Woodville SA 5011 729A Port Road Woodville SA 5011 Ph 08 8347 0000 QLD P O Box 511 Archerfield QLD 4108 2 49 Boyland Ave Coopers Plains QLD 4108 Ph 07 3373 8222 WA P O Box 2114 Midland DC W A 6936 6 91 Leach Highway Kewdale WA 6105 Ph 08 6262 8095 Or National Australian Sales Number 1300 78 FIRE 3473 For the cost of local call ...