background image

Panasonic Electric Works Nordic AB 

 

MEW01295  Rev:   2 

Technical Description  Alert Annunciation Units 1735 & 1736, ver. 1.4.x 

 

Default  for  each 

AA

  unit  is,  in  system  EBL512  and  EBL512  G3:  

Control units

 (

00, 29

), i.e. all alarms from all c.i.e:s will be presented 

in all 

AA

 units. 

Default for each 

AA

 unit is, in system EBL128:  

Zones

 (

01 - 32

), i.e. 

all alarms will be presented in all ext. FBPs. 

Summary of Contents for 1735

Page 1: ...Technical Description MEW01295 Revision 2 Alert Annunciation Units 1735 1736 ver 1 4 x Author Jan Pettersson Date of issue 2010 04 07 Date of rev 2011 08 15 ...

Page 2: ...This page has deliberately been left blank ...

Page 3: ...de via the c i e ________________ 17 6 3 Flow chart _______________________________________ 18 7 User definable text messages alarm texts ______ 20 8 Commissioning of a new unit SSD download___ 21 9 Restart ___________________________________ 23 10 Fault messages_____________________________ 25 10 1 Fault messages in the AA unit _______________________ 25 10 2 Fault messages in the c i e _________...

Page 4: ...onic Electric Works Nordic AB MEW01295 Rev 2 Technical Description Alert Annunciation Units 1735 1736 ver 1 4 x 2 15 Revision history____________________________ 35 This page has deliberately been left blank ...

Page 5: ...instructions for the system respectively The Alert annunciation units 1735 1736 shall run in SW mode 1735 1587 and SW mode 1736 1587 respectively See also chapter General description page 5 This document is valid for the 1735 1736 software version 1 4 x The Alert annunciation units 1735 1736 can be used in the systems EBL512 EBL128 and EBL512 G3 In system EBL512 G3 the 1735 1736 a software version...

Page 6: ...finitions explanations abbreviations etc frequently used or not explained elsewhere in the document AA Alert Annunciation AAU Alert Annunciation Unit AA alarm Alert Annunciation alarm AA function Alert Annunciation function C i e Control and indicating equipment control unit C U Control unit Control and indicating equipment SW Software HW Hardware ...

Page 7: ...ted The LED L4 Acknowledged Kvittering is indicating if the AA alarm has been acknowledged See also chapter Operation page 29 3 1 Alert Annunciation Unit 1735 Figure 1 The Alert Annunciation Unit AAU 1735 has a Swedish front The Alert Annunciation Unit consists of a compact size enclosure made of grey RAL 7035 high impact ABS with temperature resistance up to 85 C Fitted with a supplementary O rin...

Page 8: ...ectly to the main board connector J4 3 2 Alert Annunciation Unit 1736 Figure 2 The Alert Annunciation Unit AAU 1736 A neutral front where the designation texts by production are made separately and put into the transparent text slot for the LED and push button respectively It also holds one extra LED two extra push buttons The Alert Annunciation Unit consists of a compact size enclosure made of gr...

Page 9: ...2 1736 units running in SW mode 1736 1587 have to be connected to an Ext FBP DU interface board 1587 mounted in the EBL512 c i e EBL512 software version 2 2 is required In system EBL128 1736 units running in SW mode 1736 1587 are connected directly to the main board connector J1 but an optional RS485 transceiver component 4552 is required on the main board In system EBL512 G3 1736 units running in...

Page 10: ...n an installation the AA unit in one specific building shall only present alarms activated within this building The following so called operands are available CU alternatives not valid for EBL128 1 Control unit CU 2 Consecutive control units CU1 CU2 3 Zone zone 4 Consecutive zones zone1 zone2 5 Zone address zone addr 6 Consecutive zone addresses zone1 addr1 zone2 addr2 Explanations 1 CU Control un...

Page 11: ...iation Units 1735 1736 ver 1 4 x 9 Default for each AA unit is in system EBL512 and EBL512 G3 Control units 00 29 i e all alarms from all c i e s will be presented in all AA units Default for each AA unit is in system EBL128 Zones 01 32 i e all alarms will be presented in all ext FBPs ...

Page 12: ...e also tables below The following is valid in quiescent normal condition LED L6 Operation is turned on if the alert annunciation function is enabled3 else turned off Buzzer is silent No text in the display and no back light No button possible to use 4 In the following tables AA Alert Annunciation 3 The AA function is normally enabled during daytime disabled during night time via a time channel 4 P...

Page 13: ...ore than one alarm Use push button P1 Alarms queued to scroll L3 Fire brigade alerted Räddningstjänsten larmad Red Cont Output s for Fire brigade tx are activated 5 L4 Acknowledge Kvittering Yellow Cont All AA alarms have been acknowledged by the push button P2 Acknowledge and new AA alarms will be automatically acknowledged L5 L6 Operation Drift Green Cont The AA function is enabled Off The AA fu...

Page 14: ...apsulation is not possible to do NOTE Regarding P1 and P2 see chapter SW mode Address setting page 16 and regarding P3 chapter SW version page 27 Table of others Component Indicating Buzzer7 1 beep 5 s AA alarm Cont All LEDs turned off as well There is a CPU memory fault in the unit Display All or selected Fire alarms8 AA alarms presented like in the c i e that the AA unit is connected to and an a...

Page 15: ...h button respectively Figure 4 The Alert Annunciation Unit AAU 1736 neutral front The following is valid in quiescent normal condition LED L6 is turned on if the alert annunciation function is enabled9 else turned off Buzzer is silent No text in the display and no back light No button possible to use 10 9 The AA function is normally enabled during daytime disabled during night time via a time chan...

Page 16: ...L3 Depending on language etc Fire brigade alerted Red Cont Output s for Fire brigade tx are activated 11 L4 Depending on language etc Acknowledge Yellow Cont All AA alarms have been acknowledged by the push button P2 and new AA alarms will be automatically acknow ledged L5 Depending on language etc Extinguishing Red Cont Output s for Extinguishing are activated 11 L6 Depending on language etc Oper...

Page 17: ...esting the LEDs the buzzer and the display back light and dots NOTE This must be done only in quiescent condition NOTE Regarding P1 and P2 see chapter SW mode Address setting page 16 and regarding P3 chapter SW version page 27 Table of others Component Indicating Buzzer14 1 beep 5 s AA alarm Cont All LEDs turned off as well There is a CPU memory fault in the unit Display All or selected Fire alarm...

Page 18: ...all also have a unique address on the RS485 line connected to the main board connector J4 See EBL512 G3 Planning Instructions 6 1 SW mode setting A brand new AA unit has no SW mode It is factory set to Not selected and is hereby not addressable When it is powered it will automatically be ready for the SW mode setting As an alternative an AA unit in operation15 can be ready for the SW mode setting ...

Page 19: ...n and the following information is shown in the display ADDRESS SETTING Change Black Address XX Store Yellow XX can be changed to the following For an AA unit the address can be set to 00 15 18 Default is 00 Scroll to the wanted address with the push button P1 black Store the selected address with the push button P2 yellow and the unit will automatically restart and enter its normal operation mode...

Page 20: ...its 1735 1736 ver 1 4 x 18 menu H5 A9 A7 in system EBL512 G3 see Operating instructions for the system respectively 6 3 Flow chart On the following page is a flow chart showing the SW mode setting Language setting20 Address setting etc 20 Language setting is not valid for the AA units 1735 1736 ...

Page 21: ...scription Alert Annunciation Units 1735 1736 ver 1 4 x 19 Power on Restart Reset via JP1 J4 ON Yes No Yes No Normal operation SW mode setting SW mode xxxx 1587 No Yes Address command from c i e Language setting Address setting SW mode selected J4 ON No No Yes Yes ...

Page 22: ...these text messages will be shown instead of the text messages sent out from the c i e The priority order is as follows 1 Point alarm text stored in the AA unit 2 Zone alarm text stored in the AA unit 3 Default alarm text stored in the AA unit 4 Text sent out from the c i e When alarm texts shall be stored in all or in some AA units the unique alarm texts are created in Win512 Win128 Win512 G3 and...

Page 23: ...e F19 on the main board 5010 in the EBL512 G3 c i e i e the AA unit s will now be powered up 3 A brand new unit will automatically be ready for the SW mode setting 4 After SW mode and address setting press P2 yellow and the unit will restart see chapter Restart page 23 5 Since the SSD is not downloaded in the c i e there will be a fault message in the unit s display No contact with Control unit Al...

Page 24: ...to an AA unit the following will be shown in its display SSD download in progress 8 After download of SSD to an AA unit the following will be shown in its display very quickly SSD Download Memory OK or SSD Download Memory Fault After that the AAU will restart see chapter Restart page 23 9 The unit will then start working in normal operation mode ...

Page 25: ...cking program memory and after that very quickly Program memory OK and after that SSD memory OK All LEDs will be turned on during the restart If there is a program memory fault there will be a fault message in the display Memory fault in program area n n 1 or 2 The AA unit will not work There will also be a fault message in the c i e In system EBL512 FAULT Comm AAU xx 1587 board x CU xx In system ...

Page 26: ... memory fault The AA unit will work since the alarm texts will be sent out from the c i e There will also be a fault message in the c i e In system EBL512 FAULT SSD AAU xx 1587 board x CU xx In system EBL128 FAULT Site specific data SSD AAU x In system EBL512 G3 FAULT Site specific data alert annunciation unit control unit ...

Page 27: ...ode settings in the AA unit etc SSD memory fault See chapter Restart page 23 SSD Download Memory Fault in conjunction with SSD download see chapter Commissioning of a new unit SSD download page 21 Memory fault in program area n See chapter Restart page 23 10 2 Fault messages in the c i e 10 2 1 System EBL512 FAULT 1587 board x CU xx Fault on no communication to the 1587 board No x in control unit ...

Page 28: ...data SSD AAU x See chapter Restart page 23 10 2 3 System EBL512 G3 FAULT No reply alert annunciation unit xx control unit xx The contact with the ext AAU is interrupted Check the cable and all connections Is a correct complete SSD download via Win512 G3 performed Check the address setting SW mode setting etc See also chapter Restart page 23 FAULT Alert annuniciation unit xx The AAU is programmed v...

Page 29: ...xxxx Store Yellow press push button P2 yellow and the following will be displayed ADDRESS SETTING Change Black Address XX Store Yellow press push buttons P1 black and P2 yellow simultaneously and the following will be displayed Rst nn Addr aaaaaaaa Version V vvvv Return Yellow Erase SSD Black nn restart type code and aaaaaaaa memory address before restart nn 00 Power On Reset Power supply connecte...

Page 30: ...nd click the right mouse button In win128 and Win512 G3 in menu Tools select Download FBP EPU AAU Software Select Download program and select the SW file to be downloaded i e DU_version BIN where version is the valid program version e g 14x program version 1 4 x Check set the port and baud rate See also the Win512 Win128 Win512 G3 help 2 Connect the PC to the AA unit J2 3 Put the jumpers JP3 and J...

Page 31: ...A alarm has been acknowledged The following page figure show an operation summary for the Alert Annunciation units 1735 1736 See also chapter SW mode Address setting page 16 AA alarm acknowledged in any Alert Annunciation unit will be indicated in all Alert annunciation units AA alarm reset in any Alert annunciation unit or in the c i e will also be reset in all other Alert Annunciation units NOTE...

Page 32: ...295 Rev 2 Technical Description Alert Annunciation Units 1735 1736 ver 1 4 x 30 Figure 5 Operation summary for the AA unit 1735 The AA unit 1736 is like 1735 but it also has an LED Extinguishing and push buttons Silence alarm devices and Test ...

Page 33: ... The Alert Annunciation units 1735 1736 connections to the terminal block J1 The jumper JP8 only has to be on place shunted if the unit is the last unit on the line NOTE The AA units 1735 1736 can in EBL512 only be connected to a 1587 board not 1582 In EBL128 24 V 0V S0 S1 to terminal block J1 13 14 15 16 In EBL512 G3 24 V 0V S0 S1 to terminal block J4 35 36 37 38 Figure 7 The Alert Annunciation u...

Page 34: ...e and address setting shall be done J8 Not used in this unit J10 Not used in this unit J11 Not used in this unit JP1 Reset Restart of the unit JP2 Boot The unit has to be in bootstrap mode before SW download JP3 Pos A PC for SW download connected via J2 Pos B The unit is connected to the c i e default JP4 Pos A PC for SW download connected via J2 Pos B The unit is connected to the c i e default JP...

Page 35: ...1735 1736 this is done via jumper JP8 JP8 mounted the termination resistor is connected 14 2 1 Cable The cable to be used in systems EBL512 and EBL512 G3 is LiYCY Twisted Pairs 2 x 2 x 0 75 mm2 screened tinned copper braid or equivalent Cable length up to 1200 m theoretically but the cable length is also depending on the current consumption i e the type and number of units connected NOTE In system...

Page 36: ... Nordic AB MEW01295 Rev 2 Technical Description Alert Annunciation Units 1735 1736 ver 1 4 x 34 Unit Current consumption Quiescent mA Active mA 12 V DC 24 V DC 12 V DC 24 V DC AA unit 1735 48 26 79 42 AA unit 1736 48 26 79 42 ...

Page 37: ...unciation Units 1735 1736 ver 1 4 x 35 15 Revision history Revisions are when possible written with red font colour Revision 1 1 Info revised 3 2 Figure 2 corrected 5 1 Info added 5 2 Info added 6 1 Info added Revision 2 5 2 P3 footnote 12 added 11 1 Display text revised Info added ...

Page 38: ...Panasonic Electric Works Nordic AB MEW01295 Rev 2 Technical Description Alert Annunciation Units 1735 1736 ver 1 4 x 36 ...

Page 39: ...This page has deliberately been left blank ...

Page 40: ...Panasonic Electric Works Nordic AB Jungmansgatan 12 SE 211 19 Malmö Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 info fste eu pewg panasonic com www panasonic fire security com ...

Reviews: