Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
15
Table of push buttons:
Push button
Colour
Operation / function
P1
(Depending on
language, etc.
"Alarms queued")
Black
Used, when LED "L2" is turned on, to scroll
through the queued alarms. (The first alarm will
automatically be shown again after 20 seconds, if
no button is used during that time.)
P2
(Depending on
language, etc.
"Acknowledge")
Yellow
Used to acknowledge an
AA
alarm. The unit's
buzzer will also be silenced. (Investigation time
starts.) Acknowledged
AA
alarm is indicated by
LED "L4".
P3
(Depending on
language, etc.
"Silence alarm devices")
Red
Used to silence the alarm devices.
(Normal fire alarms &
AA
alarms.)
12
P4
(Depending on
language, etc.
"Reset")
Green
Used to reset all
AA
alarm(s). (Fire alarms, i.e.
not
AA
alarms, have to be reset in the c.i.e.). So
called "encapsulation" is not possible to do.
P5
(Depending on
language, etc.
("Test")
13
White
Used for testing the LEDs, the buzzer and the
display (back-light and dots).
NOTE!
This must
be done only in quiescent condition.
NOTE!
Regarding "P1" and "P2", see chapter "SW mode & Address
setting, page 16 and regarding "P3", chapter "SW version", page 27.
Table of others:
Component
Indicating
Buzzer
14
1 beep/5 s
AA
alarm.
Cont. +
All
LEDs
turned off as well.
There is a CPU / memory fault in the unit.
Display
All or selected Fire alarms /
AA
alarms presented like in the
c.i.e. that the
AA
unit is connected to and an alarm text (if
programmed).
(
NOTE!
A fault message may be shown,
indicating a communication fault (i.e. no connection between
the unit and the c.i.e.).
NOTE!
Regarding the Buzzer and the Display, see also chapter "SW
mode & Address setting, page 16.
12
If the "Silence alarm devices" button in the c.i.e. has been programmed to
"Disable alarm devices", "P3" will have the same function. "P3" cannot be
used until a fire or
AA
alarm is activated in the system.
13
Press "P5" (Test) for a test of the LEDs, the buzzer and the display (back-
light and dots).
NOTE!
This must be done only in quiescent condition.
14
The buzzer may be programmed as "disabled" (via Win512 / Win128 /
Win512 G3), i.e. it will never sound.