Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
12
Table of push buttons:
Push button
Colour
Operation / function
P1
Alarms queued
(Flera larm)
Black
Used, when LED "L2" (Alarms queued) is turned on,
to scroll through the queued alarms. (The first alarm
will automatically be shown again after 20 seconds,
if no button is used during that time.)
P2
Acknowledge
(Kvittering)
6
Yellow
Used to acknowledge an
AA
alarm. The unit's
buzzer will also be silenced. (Investigation time
starts.) Acknowledged
AA
alarm is indicated by
LED "L4" (Acknowledge).
P3
Reset
(Återställning)
6
Green
Used to reset all
AA
alarm(s). (Fire alarms, i.e. not
AA
alarms, have to be reset in the c.i.e.). So called
"encapsulation" is not possible to do.
NOTE!
Regarding "P1" and "P2", see chapter "SW mode & Address
setting, page 16 and regarding "P3", chapter "SW version", page 27.
Table of others:
Component
Indicating
Buzzer
7
1 beep/5 s
AA
alarm.
Cont. +
All
LEDs
turned off as well.
There is a CPU / memory fault in the unit.
Display
All or selected Fire alarms
8
/
AA
alarms presented like in the
c.i.e. that the
AA
unit is connected to and an alarm text (if
programmed).
(
NOTE!
A fault message may be shown, indicating a
communication fault (i.e. no connection between the unit and
the c.i.e.).
NOTE!
Regarding the Buzzer and the Display, see also chapter "SW
mode & Address setting, page 16.
6
Press simultaneously "P2" (Acknowledge) & "P3" (Reset) for a test of the
LEDs, the buzzer and the display (back-light and dots).
NOTE!
This must be done only in quiescent condition.
7
The buzzer may be programmed as "disabled" (via Win512 / Win128 /
Win512 G3), i.e. it will
never
sound.
8
Also Heavy smoke / heat alarms.