Test run

Preparation 

After finish the installation tasks, please check the items: 

1  Check the dip switch setting and short wiring

2   Power cable

3  Communication wire

  

Water circuit

Check if the power cable is connected correctly, and check if the screws have been screwed down.

Check if the communication wire is connected correctly.

Check if the water pipes are correctly connected, and the pipe dimensions are correct.

Check if all the shut off valve and manual valve is opened, check if all the joint is fastened.

Heatproof measures must be  taken for water outlet  pipes and water inlet. 

Please use specified cables.

Please adopt specified communication wire.

19

Water or Brine Filling

1  with water pipe connected to the unit  s water system, and open all the air exhaust valves in water system

                

.

2. Discharge the air for both domestic hot water sytem and air conditioning water system, including all usage

 and there is no air inside the water system. 

Turn on the heat pump

select heating, domestic hot water mode , check whether the unit is running properly or not,the 
compressor will be started in 3~5 minute after powered on.

Running

MOST IMPORTANT

!

3.Make sure it is not in cooling mode during first operation or test running unitl you make sure

the air conditioning circulation pump is working properly and water is recycling smoothly.

2 Select a big enough water pump for the air conditioning water circuit

1.Alway keep electricity connection with heat pump to enable the antifreeze function.

.

,

.

.

.

.

.

and fill water into the system. Keep the air exhaust valve open untill there is continous water coming out

of the air exhaust valve. Then close the air exhaust valve.

terminals such as domestic hot water tank, fan coils,radiators and etc. To make sure all system are full of water

Note!

To avoid the heat pump to be frozen, if the air temp is possible to be under zero degree in winter,you need 

.

to use brind(glycol) to replace pure water in case of electricity cut off accident during winter

Summary of Contents for H Series

Page 1: ...AIR TO WATER HEAT PUMP Installation and Operation Manual DC INVERTER DC INVERTER H series Only Heating series AC series Heating Cooling series HC series Mutifunctional Heating Cooling Hot water...

Page 2: ...Content Safety Precautions Transport and storage General 2 2 2 3 4 11 12 17 19 1 Components Wired LCD Controller Error Code Installation Electric connection Test run...

Page 3: ...ntial hazard of leakage of inflammable gas If the foundation is unstable the outdoor unit may drop and cause a casualty accident so this must be validated carefully Make sure that the foundation of in...

Page 4: ...way valve 1 2 3 4 5 6 7 8 9 10 12 13 14 15 16 17 18 19 Position Position Component Component Compressor Gas liquid isolator Water inlet Drain Needle valve AH 6 AH 8 AH 11 AH 15DC 2 3 4 1 5 6 7 19 20...

Page 5: ...hen decrease by 1 5 Key up it s a combined key also but opposite to down key Continuous press then continuous increase short press then increase by 1 6 Key confirm confirm previous operations 7 Key mo...

Page 6: ...can change parameter according to need 3 Procedures of setting parameter change A When in settled mode the unit will operate in accordance with the factory default temperature or last modified temper...

Page 7: ...hes and shows the original or default value default value is 10 followed by press key or to change minimum is 10 maximum no more than 99 after that press key to confirm and exit change mode If didn t...

Page 8: ...rotection temp 100 129 2 57 check set 13 reserved 14 function parameter 0 G3 is seasonal switch valve 1 G3 is solar pre heat valve 0 check set 19 adjust fixed running rate 0 100 HZ 50HZ check set 20 R...

Page 9: ...input status 0 DHW invalid 1 DHW valid check 09 Switch input status 0 G1 valid 1 G1 invalid check 10 high pressure swithc status 0 off 1 on check 11 overcurrent protect switch status 0 off 1 on check...

Page 10: ...pump has water source Icon If it has timer on off setting there is timer icon to indicate 29 C4 water pump 1 run 0 stop check 30 C5 water pump 1 run 0 stop check 31 C6 water pump 1 run 0 stop check 32...

Page 11: ...n to indicate 9 way of communication Non polarity double wire maximum running length is 100 meters and point to point connected Back view of wired controller showed below after change need be repowere...

Page 12: ...Only for Inverter outdoor unit F3 Compressor stopped abnormally Red and shining Only for Inverter outdoor unit F4 outdoor module radiator tansducer error Red and shining Only for Inverter outdoor unit...

Page 13: ...Method 1 12 Method 2 DHW with Room Heating Installation 1 Installationmethod...

Page 14: ...water pump connection can be found in wiring diagram 4 Safety valve air discharge valve should be installed at the top of the circulation system for easy air discharge Air conditoning circulation can...

Page 15: ...Application 1 Application 2 14 Installation 2 Installation with solar assistant...

Page 16: ...ation 15 G2 G1 DHW and AC switching valve G2 Solar automatic selection valve W B D H A 5 4 Unit Dimension mm AH 6 AH 8 AH 11 AH 15 W 1091 1091 D 400 400 H 880 980 Installation 1091 400 780 A 412 412 B...

Page 17: ...of accumulated water in rainy season In snowy areas it is important to prevent accumulated snow from blocking up the air out The recommended height is 20cm to 30cm 2 Drain ditch or other facilities sh...

Page 18: ...s Note Electrical installation and service must be carried out under the supervision of a qualified electrician Electrical installation and wiring must be carried out in accordance with the stipulatio...

Page 19: ...Electric connection Wiring Diagram with built inside water circulation pump Wiring Diagram No built inside water circulation pump 18...

Page 20: ...g all usage and there is no air inside the water system Turn on the heat pump select heating domestic hot water mode check whether the unit is running properly or not the compressor will be started in...

Reviews: