. UNIT OPERATION

 

 

6

 Parameter Checking and setting 

Please press key M+

▲ for 3 seconds and enter to parameter setting mode as show below.   

 

“01”is  parameter  code,“78”is  parameter  values.    Other  items’  parameters  meaning  are  the  same  with  above 

picture showed.   

 

 

 

Parameter list: 

  

NO. Name 

range/meaning 

default status  remark 

00 

power off auto restart 

0

not restart

1

Auto restart 

1 check/set 

 

01 

hot water temp return differential 

2~15

℃,

minus return differential 2

 

check/set  

02 

air conditioning return differential 

2~15

℃,

minus return differential 2

 

check/set  

03 

defrost start temp. 

-20~5

 

0

 

check/set  

04 

water source anti-freeze temp. 

-20~5

 

2

 

check/set  

05 

antifreeze exist temp. 

-5

5

 

5

 

check/set  

06 

defrost exist temp. 

10~35

 30

 

check/set  

08 

Interval between 2 defrosts 

15~99 mins 

35 

check/set   

09 

ambient temp of DHW backup   

electrical heater start   

-20~20

 

0

 

check/set  

10 

ambient temp of AC backup 

electrical heater start 

-20~20

 

0

 

check/set  

11 reserved 

 

 

 

 

12 

Exhaust gas protection temp. 

100~129

/2

 

57 check/set 

 

13 reserved 

 

 

 

 

14 function 

parameter 

0

G3 is seasonal switch valve

1

G3 is solar pre-heat valve

 

0 check/set 

 

19 

adjust fixed running rate 

0~100 HZ 

50HZ

check/set 

 

20 

Run set rate   

1

practical running

   

0

manual rate running 

check/set 

 

Note

   

Usage of    14.    Function parameter: (As per solar application 1) 

when this parameter is 1, when air conditioning heating run, it will compare solar water tank temp with air conditioning returned 

water temp, when solar water tank temp is 5 or more degree higher than air conditioning returned temp, the 3-way valve G3 

electricity supply will be on; when solar water tank temp - air conditioning returned temp is less than 2 centigrade, G3 electricity 

supply will be off. This function is to use solar to preheat for room heating and DHW tank water. 

When this parameter is 0, G3 is seasonal switch valve, when the heat pump is working for heating, G3 is on, when heat pump is 

working for cooling, G3 is off. 

Normally use one 3-way valve with 3 wires.    2 wires are always connected with electricity supply and 1 signal wire is connected 

with heat pump G3 terminal port to enable function. 

 

7

Summary of Contents for H Series

Page 1: ...AIR TO WATER HEAT PUMP Installation and Operation Manual DC INVERTER DC INVERTER H series Only Heating series AC series Heating Cooling series HC series Mutifunctional Heating Cooling Hot water...

Page 2: ...Content Safety Precautions Transport and storage General 2 2 2 3 4 11 12 17 19 1 Components Wired LCD Controller Error Code Installation Electric connection Test run...

Page 3: ...ntial hazard of leakage of inflammable gas If the foundation is unstable the outdoor unit may drop and cause a casualty accident so this must be validated carefully Make sure that the foundation of in...

Page 4: ...way valve 1 2 3 4 5 6 7 8 9 10 12 13 14 15 16 17 18 19 Position Position Component Component Compressor Gas liquid isolator Water inlet Drain Needle valve AH 6 AH 8 AH 11 AH 15DC 2 3 4 1 5 6 7 19 20...

Page 5: ...hen decrease by 1 5 Key up it s a combined key also but opposite to down key Continuous press then continuous increase short press then increase by 1 6 Key confirm confirm previous operations 7 Key mo...

Page 6: ...can change parameter according to need 3 Procedures of setting parameter change A When in settled mode the unit will operate in accordance with the factory default temperature or last modified temper...

Page 7: ...hes and shows the original or default value default value is 10 followed by press key or to change minimum is 10 maximum no more than 99 after that press key to confirm and exit change mode If didn t...

Page 8: ...rotection temp 100 129 2 57 check set 13 reserved 14 function parameter 0 G3 is seasonal switch valve 1 G3 is solar pre heat valve 0 check set 19 adjust fixed running rate 0 100 HZ 50HZ check set 20 R...

Page 9: ...input status 0 DHW invalid 1 DHW valid check 09 Switch input status 0 G1 valid 1 G1 invalid check 10 high pressure swithc status 0 off 1 on check 11 overcurrent protect switch status 0 off 1 on check...

Page 10: ...pump has water source Icon If it has timer on off setting there is timer icon to indicate 29 C4 water pump 1 run 0 stop check 30 C5 water pump 1 run 0 stop check 31 C6 water pump 1 run 0 stop check 32...

Page 11: ...n to indicate 9 way of communication Non polarity double wire maximum running length is 100 meters and point to point connected Back view of wired controller showed below after change need be repowere...

Page 12: ...Only for Inverter outdoor unit F3 Compressor stopped abnormally Red and shining Only for Inverter outdoor unit F4 outdoor module radiator tansducer error Red and shining Only for Inverter outdoor unit...

Page 13: ...Method 1 12 Method 2 DHW with Room Heating Installation 1 Installationmethod...

Page 14: ...water pump connection can be found in wiring diagram 4 Safety valve air discharge valve should be installed at the top of the circulation system for easy air discharge Air conditoning circulation can...

Page 15: ...Application 1 Application 2 14 Installation 2 Installation with solar assistant...

Page 16: ...ation 15 G2 G1 DHW and AC switching valve G2 Solar automatic selection valve W B D H A 5 4 Unit Dimension mm AH 6 AH 8 AH 11 AH 15 W 1091 1091 D 400 400 H 880 980 Installation 1091 400 780 A 412 412 B...

Page 17: ...of accumulated water in rainy season In snowy areas it is important to prevent accumulated snow from blocking up the air out The recommended height is 20cm to 30cm 2 Drain ditch or other facilities sh...

Page 18: ...s Note Electrical installation and service must be carried out under the supervision of a qualified electrician Electrical installation and wiring must be carried out in accordance with the stipulatio...

Page 19: ...Electric connection Wiring Diagram with built inside water circulation pump Wiring Diagram No built inside water circulation pump 18...

Page 20: ...g all usage and there is no air inside the water system Turn on the heat pump select heating domestic hot water mode check whether the unit is running properly or not the compressor will be started in...

Reviews: