76
004778560 - 17/11/2020
technical data sheet at the end of the booklet.
A non-closable permanent aeration grid must
be placed externally; in areas that are particularly
windy and exposed to weathering, provide rain
and wind protection.
Ensure that the air intake is positioned so that it
won't be accidentally obstructed.
If it is impossible to create an external air intake
in the wall behind the appliance (non-perimeter
wall), a hole must be made in an external wall of
the room where the appliance is positioned.
If it is not possible to create the fresh air intake in
the room, an external hole can be created in an
adjacent room provided it is permanently inter-
connected by means of a transfer grille.
It is forbidden to take combustion air from ga-
rages, warehouses of combustible material or
places with activities at risk of fire.
If there are other heating appliances in the room,
the combustion air inlets must guarantee the
necessary volume of air for the correct operation
of all devices.
If one or more extraction fans (extrac-
tor hoods) are present and operating
in the installation room, combustion
malfunctions may occur due to lack of
combustion air.
6.5 Flue gas fitting
The appliance works with the combustion cham-
ber at negative pressure. It is therefore essential
to make sure that the flue gas evacuation is
airtight (this is the responsibility of the installer).
The appliance must be connected to its own flue
gas duct, not shared, and which is suitable for
ensuring adequate dispersion of the combustion
products into the atmosphere, in accordance
with the regulations in force in the country of
installation.
The components making up the flue
gas ducting system must be declared
suitable for the specific operating con-
ditions and provided with CE marking.
It is mandatory to create a first vertical
section measuring at least 1.5 meters to
guarantee correct expulsion of the flue
gases.
It is advisable to make a maximum of 3 direction
changes, in addition to that resulting from the
rear connection of the appliance to the chimney,
using 45 - 90 ° bends or Tee fittings (
).
Always use a Tee fitting with inspection cap at
each horizontal and vertical change of the flue
gas route (
).
The horizontal sections must have a maximum
length of 2-3 m with an upward slope of 3-5%
Anchor the pipes with suitable collars to the wall.
The flue gas fitting MUST NOT BE connected:
• to a chimney used by other generators (boilers,
stoves, fireplaces, etc. ...);
• to air extraction systems (hoods, vents etc. ...)
even if "ducted".
It is forbidden to install shut-off and draught
valves.