Operation and Maintenance Documentation

8.

    ELECTRICAL CONNECTION DIAGRAMS

MAKE THE ELECTRICAL CONNECTION OF THE CONTROLLER IN PHASE CORRECTLY, MAKE SURE TO 

CONNECT THE PHASE TO ONE OF POINT “U” AND NULL TO POINT “N”.

Any and all repair and maintenance works must be conducted with the power off and the heat input 

disconnected.

Only suitably qualified staff well acquainted with the safety regulations concerning handling with an 

electrical device must be employed when the device is being installed, started and operated!

 

To connect the curtain use a 3-core copper cable of minimal diameter 3x1,5mm² for two curtains (up to 6 fans) or 3x2,5mm² for 3 cur-

tains (up to 9 fans). The electrical installation and connection to power supply must be done in compliance with the existing regulations 

and standards for building industry.

The electric network, to which the device is to be connected, should protect the device against overloading and short circuit. It is neces-

sary to use protective grounding. Any electrical installation works and the connection to supply power must be conducted in accordance 

with the applicable building regulations and standards. The connection of the unit to the power supply must be conducted by a qualified 

specialist who is familiar with the Manual. Fan’s motor is equipped with internal thermal protection against overheating. Power cable 

and a main switch are not included in the set.

Also the DOORSTOP door contact switch can be installed; it turns off the ACR Pro curtain when the door is being closed and the mo

-

ment the door is being opened the ACR Pro curtain starts operating accordingly to the parameters set in the control panel of the device.

Fan wiring description:

PE (yellow/green): 

earth protection

U3 (red):

 

low speed

U2 (grey):

 

middle speed

U1 (brown):

 

high speed

N (blue):

 Null

AFTER A YEAR OF OPERATION CHECK THE ELECTRICAL CONNECTIONS AND IF NEEDED TIGHTEN  

THE WIRE CONNECTIONS TO ELIMINATE POTENTIAL SPARKLING.

 

• 

Before making the electrical connection, make sure that the mains voltage and mains frequency correspond to the values 

indicated on the rating plate of the appliance�

• 

Do not start the appliance without connecting the earth-ground!

Electrical connection for ACR Pro E (PTC electric heat exchanger)

•  Power supply for PTC heaters are 3x400V/50Hz!

•  For ACR Pro 1500E use wire min. 5x6mm

2

, fuse B25

•  For ACR Pro 2000E use wire min. 5x6mm

2

, fuse C32

 

The Multi 6 control box allows to connect and control up to 6x ACR Pro 2000 and 6x servomotors. The control of the unit motors is via 

COMFORT or INTELLIGENT controller, there is a possibility to connect DOORSTOP switch to it. The thermostat has a primary function 

when connected to the unit with the DOORSTOP. In order to connect more than 6 air curtains there is a possibility of connecting up 

to 10 Multi 6 controls in serial. To do so in to remove the DS-N jumper in the first Multi 6 box and install DS-N jumper in all the other 

boxes.

Summary of Contents for ACR PRO

Page 1: ...eration and Maintenance Documentation www pakole com ACR_Pro_008_025_011_210617_V004_EN Type ACR Pro ACR Pro 1500H ACR Pro 2000H ACR Pro 1500C ACR Pro 2000C ACR Pro 1500E ACR Pro 2000E ACR PRO AIR CUR...

Page 2: ...SAFETY PRINCIPLES 3 2 PURPOSE OF THE DEVICE 4 3 BASIC TECHNICAL PARAMETERS 4 4 DIMENSION 5 5 HEAT OUTPUT RANGES 6 6 ASSEMBLY 7 7 CONTROLLER INSTALLATION 9 8 ELECTRICAL CONNECTION DIAGRAMS 11 9 WATER C...

Page 3: ...tain is connected directly to the cable please make sure there is a splitter protecting against any undesired discon necting Pay special attention while transporting the device not to damage the casin...

Page 4: ...ehouse and production halls Loading unloading sections in supermarkets and large commercial premises Car showrooms and service stations exhibition surfaces 3 BASIC TECHNICAL PARAMETERS for water param...

Page 5: ...5 Acr Pro air curtains Operation and Maintenance Documentation 4 DIMENSIONS ACR Pro 1500H ACR Pro 1500E ACR Pro 1500C ACR Pro 2000H ACR Pro 2000E ACR Pro 2000C...

Page 6: ...n the heaters surface as well as larger energy exchange surface ACR Pro 1500H inlet outlet water temperature 60 40 70 50 80 60 90 70 inlet air temperature 0 5 10 15 20 0 5 10 15 20 0 5 10 15 20 0 5 10...

Page 7: ...work is possible to be conducted On both connection nozzles manual shut off valves should be installed in case of the necessity of disconnecting the unit The hot water medium supply must be connected...

Page 8: ...utlet of the curtain is as close as possible to the doorway and air gap is at the height of the upper edge of the entry Please make sure to keep the distance of about 300 mm between the outlet casing...

Page 9: ...UARD PRO Control room temperature by opening closing the vale or by adjusting air volume automatically Antifreeze mode protection against dropping room temperature below critical level 5 15 C Possibil...

Page 10: ...FAN Change of the fan speed to low medium high or automatic Hold FAN for 5 seconds Manual calendar programming Monday Friday Saturday Sunday 6 settings per day BMS Functions When Panel Intelligent is...

Page 11: ...ating Power cable and a main switch are not included in the set Also the DOORSTOP door contact switch can be installed it turns off the ACR Pro curtain when the door is being closed and the mo ment th...

Page 12: ...curtains Operation and Maintenance Documentation 8 1 Connection scheme for 1 unit ACR Pro H or C type with Comfort controller ACR Pro E 8 2 Connection scheme for 1 unit ACR Pro E type with Comfort con...

Page 13: ...urtains Operation and Maintenance Documentation 8 3 Connection scheme for ACR Pro H or C type with custom controller 8 4 Connection scheme for ACR Pro E type with custom controller ACR Pro ACR Pro ACR...

Page 14: ...Acr Pro air curtains Operation and Maintenance Documentation 8 5 Connection scheme for 6 unit ACR Pro H or C type with Multi 6 and Comfort ACR Pro ACR Pro ACR Pro ACR Pro ACR Pro ACR Pro ACR Pro ACR P...

Page 15: ...Pro air curtains Operation and Maintenance Documentation 8 6 Connection scheme for 6 unit ACR Pro E type with Multi 6 and Comfort ACR Pro E ACR Pro ACR Pro E ACR Pro E ACR Pro E ACR Pro E ACR Pro E AC...

Page 16: ...s made of copper as well as other elements of the hy draulic system circulation The liquid must be diluted with water accordingly to the manufacturer s recommendation NOTICE Any and all repair and mai...

Page 17: ...suitable part and mending which is done by not authorized retailer or service station The regular maintenance is the owner s responsibility The manufacturer does not assume the responsibility in case...

Page 18: ......

Page 19: ......

Page 20: ...PAKOLE TRADE Kft H 8000 Sz kesfeh rv r B rg ndi t 8 10 www pakole com mail pakole hu Tel 36 22 316 484 Fax 36 22 316 074 www pakole com...

Reviews: