SECTION 3 INSTALLATION
36
3.2
OUTPUT VOLTAGE RANGE CONFIGURATIONS
This paragraph describes the configuration of the Output Voltage Range for the ASX-Series Power
Source. The ASX-Series Power Source can be configured for several different Output Voltage
Ranges. The standard output configurations are:
1)
- 0-132
VAC
l-n
Direct-Coupled Output, standard on Models
115-ASX, 160-ASX, 315-ASX, and 360-ASX
0-135
VAC
l-n
Direct-Coupled Output, standard on Models
140-ASX, 345-ASX, and 3120-ASX
0-150
VAC
l-n
Direct-Coupled Output, standard on Models
120-ASX and 320-ASX
2)
VR1.5
0-198
VAC
l-n
Models 115-ASX, 160-ASX, 315-ASX, &
360-ASX equipped with Magnetics Option
0-203
VAC
l-n
Models 140-ASX, 345-ASX & 3120-ASX
equipped with Magnetics Option
3)
VR2.0
0-264
VAC
l-n
Models 115-ASX, 160-ASX, 315-ASX, &
360-ASX equipped with Magnetics Option
0-270
VAC
l-n
Models 140-ASX, 345-ASX & 3120-ASX
equipped with Magnetics Option
4)
VR2.5
0-330
VAC
l-n
Models 115-ASX, 160-ASX, 315-ASX, &
360-ASX equipped with Magnetics Option
0-338
VAC
l-n
Models 140-ASX, 345-ASX & 3120-ASX
equipped with Magnetics Option
The
0-132
l-n
, 0-135
l-n
, and 0-150
l-n
VAC output ranges are direct-coupled outputs and are always
available. The remaining output voltage ranges are transformer-coupled. Only one is available
when output transformers are installed. However, systems can be reconfigured for a different
range, if required.
Configuration of the output voltage range is set at the time of order. Systems are configured at the
factory as ordered. The System ID label or Magnetics Module ID label will state the factory
configured voltage range. If the output voltage range specified on the System ID label or
Magnetics Module ID label is that which is desired, no further action is required. Otherwise,
reconfiguration is required.
Configuration of the Output voltage consists of
1) Verifying that the appropriate output transformer taps have been selected.
2) Verifying the proper setting of the Transformer Ratio Setting within the UPC.
3) Verifying the proper setting of the Amps to Volts Ratio Setting within the UPC
4) Calibration of the system.
Configuration varies from model to model. The following paragraphs describe the configuration
settings of the available standard output ranges. Refer to the appropriate paragraph for details.
When custom output transformers have been installed, refer to Section 9, Modifications. The
instructions stated in Section 9 take precedence over those listed in the following paragraphs.