![Pacific Power Source ASX series Operation Manual Download Page 17](http://html.mh-extra.com/html/pacific-power-source/asx-series/asx-series_operation-manual_746368017.webp)
SECTION 2 SPECIFICATIONS
9
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 160-ASX
INPUT VOLTAGE
The Model 160-ASX accepts one of the following three phase input voltages:
1) 208 VAC
Δ
±10%, 47-63 Hz
2) 220 VAC
Δ
±10%, 47-63 Hz
3) 240 VAC
Δ
±10%, 47-63 Hz
4) 220/380 VAC ±10%, 47-63 Hz
5) 230/400 VAC ±10%, 47-63 Hz
6) 240/416 VAC ±10%, 47-63 Hz
(cost option) 7) 277/480 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 160-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in
INPUT CURRENT
SERVICE RECOMMENDED
1) 208
VAC
Δ
20
A
rms
30
A
2) 220
VAC
Δ
18
A
rms
30
A
3) 240
VAC
Δ
16
A
rms
25
A
4)
220/380 VAC
11 A
rms
15
A
5)
230/400 VAC
10 A
rms
15
A
6)
240/416 VAC
10 A
rms
15
A
7)
277/480 VAC
8 A
rms
15
A
MODEL 315-ASX
INPUT VOLTAGE
The Model 315-ASX accepts one of the following single phase input voltages:
1)
100 VAC ±10%, 47-63 Hz
2)
110 VAC ±10%, 47-63 Hz
3)
120 VAC ±10%, 47-63 Hz
4)
200 VAC ±10%, 47-63 Hz
5)
208 VAC ±10%, 47-63 Hz
6)
220 VAC ±10%, 47-63 Hz
7)
230 VAC ±10%, 47-63 Hz
8)
240 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 315-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in
INPUT CURRENT SERVICE RECOMMENDED
1)
100 VAC
22 A
rms
25
A
2)
110 VAC
20 A
rms
25
A
3)
120 VAC
18 A
rms
25
A
4)
200 VAC
11 A
rms
15
A
5)
208 VAC
10 A
rms
15
A
6)
220 VAC
10 A
rms
15
A
7)
230 VAC
9 A
rms
15
A
8)
240 VAC
9 A
rms
15
A