SECTION 4 OPERATION
86
4.4 SYSTEM
TURN-OFF
This paragraph describes the procedure used to turn off the AMX-Series Power Source.
The AMX-Series Power Source is turned off by:
1.
Setting the OUTPUT POWER Switch to the
OFF
position.
2.
Opening the INPUT POWER circuit breaker
.
4.4.1 SYSTEM TURN-OFF, MODELS 390 and 3120-AMX
This paragraph describes the procedure used to turn off the 390 and 3120-AMX Power
Sources.
The 390 and 3120-AMX Power Sources are turned off by:
1.
Setting the OUTPUT POWER Switch of the Master chassis (which has the controller
installed) to the
OFF
position.
2.
Opening the INPUT POWER circuit breaker of the Slave chassis.
3.
Opening the INPUT POWER circuit breaker of the Master chassis.
CAUTION
It is recommended that only the OUTPUT POWER switch of the Master chassis be used to remove
power to a load. The INPUT POWER switch of the Slave chassis should never be turned to the
OFF
position with a load attached to the system as it will subject the Master chassis to all the load current
being delivered by the system. This will cause an overtemp shutdown if the load exceeds the Master
chassis' system ratings. Also, the Master chassis INPUT POWER switch should never be used to
remove power to a load since it drives all the control circuits for the paralleled system.
Summary of Contents for AMX Series
Page 1: ...AMX SERIES AC POWER SOURCE OPERATION MANUAL PACIFIC POWER SOURCE ...
Page 2: ......
Page 8: ......
Page 114: ......