Fireplace hearth requirements: (Measured without the insert)
The hearth may be fl ush with or raised above an adjacent combustible fl oor and must extend 16”(406mm) in front and
8”(203mm) beyond each side of the fi replace opening.
Ember protection:
Combustible fl oor in front of the fi replace insert must be protected from hot embers by non-combustible material ex-
tending 16”(406mm) (USA) and 18”(457mm) (CANADA) to the fi ring side and 8”(203mm) to other sides of the unit.
Consult CAN/CSA-B365 Installation Code for Solid-Fuel-Burning appliances and equipment in Canada, and N.F.P.A.
211 Standard for chimneys, fi replaces, vents and Solid-Fuel-Burning appliances in USA.
16”(406mm) USA
18”(457mm) CANADA
Non-combustible hearth
Non-combustible fl oor
covering
15”
381mm
*
**
**
MINIMUM EMBER
PROTECTION
DIMENSIONS
MINIMUM FIREPLACE
OPENING AND HEARTH
DIMENSIONS
18”(457mm) USA
20”(508mm) CANADA
24”
610mm
8”
203mm