Pacific energy Classic Gas Installation And Operating Insctruction Manual Download Page 11

11

VENT TERMINAL  CLEARANCES

Minimum clearances to the vent teminal must be maintained as shown in
figures #10 and #11. Measure clearances to the nearest edge of termination
hood.

NOTE:  Vent terminal must not be recessed into a wall or siding. Follow
vent terminal manufacturers installation instructions.

NOTE:  LOCAL CODES OR REGULATIONS MAY REQUIRE DIFFERENT
CLEARANCES.

Fig # 11

a

 = clearances above the roof line [in USA 12 inches (30 cm)

minimum] [in Canada 24 inches (610 cm) minimum]

b

 = clearance to an adjacent wall [24 inches (610 cm) minimum]

a

b

FIXED

CLOSED

FIXED

CLOSED

OPEN-
ABLE

OPEN-
  ABLE

VENT TERMINAL

MINIMUM

CLEARANCES

INSIDE

CORNER

DETAIL

Fig # 10

AIR SUPPLY INLET

VENT TERMINAL

GAS METER

AREA WHERE TERMINAL
IS NOT PERMITTED

1

   

In accordance with current CSA B149, Natural Gas & Propane Installation Code

 

In accordance with current ANSI Z223.1 NFPA 54, National Fuel Gas Code

*

 These numbers are only estimates. Clearance in accordance with installation codes and the requirements of the gas supplier

   

Vent shall not terminate directly above a sidewalk or paved driveway located between two single family dwellings & it serves both dwellings

+

 Permitted only if verandah, porch, deck, or balcony is fully open on a minimum or two sides beneath the floor.

Canadian Installation

1

American Installation

2

Clearance Description

A

Above grade, verandah, porch, deck, or balcony.

B

12" (30 cm)

9" (23 cm)

From window or door that may be opened.

C

From permanently closed window (condensation).

D

To ventilated soffit located above the terminal, within a horizontal
 distance of 2' (60 cm) from center-line of terminal.

E

To unventilated soffit.

F

To outside corner.

G

To inside corner.

H

3' (91 cm) within height of 

3' (91 cm) within height of 

To each side of center-line extended above a meter/regulator 

15' (4.5 m) above meter/regulator

15' (4.5 m) above meter/regulator* assembly.

I

3' (91 cm) within height of 

3' (91 cm)*

Around service regulator vent outlet.

J

12" (30 cm)

9" (23 cm)

To non-mechanical air supply inlet to building, or the combustion
air inlet to any other appliance.

K

6' (1.83 m)

3' (91 cm) above if within 

To mechanical air supply inlet.

10' (3 m) horizontally

L

7' (2.13 m)

t

7' (2.13 m)*

t

Above public paved sidewalk/driveway.

M

12" (30 cm)

+

12" (30 cm)*

+

Under verandah, porch, deck, or balcony.

N

To any horizontal surface, for roof terminations.

O

Above roof line, for roof terminations.

12" (30 cm)*

12" (30 cm)

12" (30 cm)

12" (30 cm)*

12" (30 cm)*
12" (30 cm)*

24" (60 cm)*

18" (45 cm)*

Summary of Contents for Classic Gas

Page 1: ...s supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier IMPORTAN...

Page 2: ...F TERMINATION VENTING 9 VENT RESTRICTOR ADJUSTMENT 10 VENT TERMINAL CLEARANCES 11 GLOWING EMBERS 12 INPUT RATE CONVERSION 13 PROPANE CONVERSION 14 LOG SET 15 LIGHTING INSTRUCTIONS 16 FIRST FIRE 16 OPE...

Page 3: ...ith your furnace heat exchanger or cook stove oven Super 27 Gas Classic Gas LegModel PedestalModel Fig 1 CAUTION FOR YOUR SAFETY Do not install or operate your Pacific Energy heater without first read...

Page 4: ...panel removed crackedorbroken Replacementofglassshould be done by a licensed or qualified service person Do not strike or otherwise impact the glass in anyway that may cause it to break If the glass...

Page 5: ...on the back of the unit 5 Align the pedestal mounting holes with the studs on the stove 6 Secure the pedestal to the stove with the 1 2 nuts and washers previously removed 7 Carefully place the unit...

Page 6: ...round air openings and combustion air supplies are required FLOOR PROTECTION Both the Classic Gas and Super 27 Gas Heaters may be installed directly on a combustible floor If the appliance is to be in...

Page 7: ...ng the vent system the installer should read these instructions to ensure proper installation requirements are maintained Follow vent pipe manufacturer s instructions for assembly and installation Fig...

Page 8: ...or horizontal runs greater than 1 foot increase vertical rise equally At 4 feet of rise the horizontal run may increase up to and must not exceed 10 feet A maximum of two 90 or 45 elbows may be used I...

Page 9: ...e of up to 40 feet is permitted with no horizontal offset If an offset is required ensure that the vertical rise is 1 foot greater than the horizontal offset Horizontal offset must not exceed 10 feet...

Page 10: ...llation If necessary adjust damper position as follows Damper position correction The damper position is correct if the rear right flame has the following characteristics flame has yellow colour and s...

Page 11: ...t serves both dwellings Permitted only if verandah porch deck or balcony is fully open on a minimum or two sides beneath the floor Canadian Installation1 American Installation2 Clearance Description A...

Page 12: ...off 950 Vinyl Shield Protector SV 4 VS Round Ceiling Support Wall Thimble 940 Cathedral Ceiling Support Box 941 Adjustable Square Cathedral Ceiling Support SV 4 CSB Collar for Square Cathedral Ceiling...

Page 13: ...5 Remove the burner tube by moving it to the right and up Note the location of the air shutter adjustment rod and where it passes through the burner plate 6 Using a 1 2 wrench remove the 41750 Btu or...

Page 14: ...to gain access to the orifice 3 Remove the orifice with a 5 32 4 mm hex key and replace it with the one supplied with the kit Natural gas orifice marked 62 Propane orifice marked 35 4 Reinstall the re...

Page 15: ...All logs are numbered on the underside for their order of assembly Handle logs carefully as they are very fragile Position the logs as indicated by pictures below Note Improper placement of logs may c...

Page 16: ...ice technician or gas supplier 9 Turn gas control knob counter clockwise to On position 10 Turn HI LO burner control knob to desired setting 11 Close bottom grill and turn on the burner switch 12 Turn...

Page 17: ...to be lit when the appliance is at operating temperature Let the appliance cool down approx 60 sec before attempting to relight the pilot DO NOT use force to rotate the control knob PRIMARY AIR ADJUST...

Page 18: ...ontrol valve or control wiring system of this unit No electrical connection is required for this system operation The self generating pilot provides current for the remote wall switch or wall thermost...

Page 19: ...et at a desired setting the blower will automatically turn on The blower will automatically turn off a few minutes after the appliance is shut down The blower may also be operated manually Push the ro...

Page 20: ...LD ASSEMBLY CLSU 7015 16 FIREBOX TOP SHIELD 7037 17 TRAY TUBE BURNER ASSEMBLY BRNA 7045 18 FLUE ADAPTER GASKET 2761 19 VENT ADAPTER 5096 812 20 CONTROL PANEL BRNA 7043 21 FIREBICK 9 x 4 1 2 x 1 1 4 50...

Page 21: ...X TOP SHIELD 7037 17 TRAY TUBE BURNER ASSEMBLY BRNA 7045 18 FLUE ADAPTER GASKET 2761 19 VENT ADAPTER 5096 812 20 CONTROL PANEL BRNA 7043 21 FIREBICK 9 x 4 1 2 x 1 1 4 5096 99 22 LEG ADAPTER DOOR LGAD...

Page 22: ...URNER ORIFICE 41 750 BTU NG 5021 332 A BURNER ORIFICE 25 000 BTU NG 5021 32 BURNER ORIFICE 32 000 BTU LP 5022 1 9 SCREW 8 X 1 2 BLACK 5041 10 SCREW 8 X 1 2 PLATED 5041 1 11 WASHER FIBER 5043 12 SPRING...

Page 23: ...23 RATING LABEL PROPANE CONVERSION RATING LABEL...

Page 24: ...24 Pacific Energy Fireplace Products Ltd 2975 Allenby Rd Duncan B C V9L 6V8 Phone 250 748 1184 Web site http www pacificenergy net Printed in Canada...

Reviews: