6.1
Default parameters
Solar Eclipse is already set by default to run with the following parameters:
•
Batteries stationed flat plate Gel / AGM 48 V - (30% DoD)
•
Capacity 100 Ah in ten hours (other capabilities selecting "dip switch") - 400 Ah
•
12 photovoltaic modules in series of 60 cells (string Voc about 450 V)
•
Dynamic IP address (DHCP active)
•
Charge/Discharge batteries in C10
Through the configurator software and USB / RS485 interface (or with browser) you can also select
different types of batteries such as commercial, AGM flat plate, tubular type OPzV, OPZS, Aquion and
Pylontech Lithium. The capacity is adjustable from 25 Ah to 200 Ah. For each of these types, standard
charge cycle values are reset as shown in Table 7:
Parameters
Unità
Misur
a
Car and
Commercia
l Lead
Flat Plate
Lead
AGM,
Gel type
Tubular
Plate
Lead Gel
Opzv
type
Tubular
Stationar
y Lead
Opzs
type
Aquion
Lithium
End-of-
Charge
Voltage
Volt
57,5
56,5
56,5
57,5
57,6
54,0
Holding
Voltage
Volt
54,5
54,5
54,5
54,5
54,0
53,5
Power
Limitation
Threshold
(Derating)
Volt
45,0
45,0
45,0
45,0
47,5
47,0
Low Voltage
Protection
Threshold
Volt
44,0
44,0
44,0
44,0
46,5
46,5
Deep
discharge
threshold
Stand-by
Volt
46,0
46,0
46,0
46,0
48,5
47,5
Charge time
C*10
10
10
10
10
8
5
Discharge
time
C*10
10
10
10
10
8
5
Dept of
Discharge
(Dod)
%
20
30
50
60
70
80
Equalization
voltage
Volt
60,8
-
-
60,8
-
Numer of
cycles
1000
1500
2500
2800
3750
5000
Battery stop
temperature
°C°
45,0
45,0
45,0
45,0
45,0
45,0
Table 7
–
Default parameters for generic batteries