If the voltage is correct (43 <V <55) disassemble the installer door, check the internal
battery fuses on the right side of the power board inside the Solar Eclipse
•
If the fuses are interrupted check the polarity of the connections and replace the fuses (3
fuses 10 A 6x 32 AT type)
•
If the fuses are not interrupted contact P800SRL Technical Support
SOLAR ECLIPSE DOES NOT START (first led to the left flashing)
•
Verify that Solar Eclipse is on (LEDs on)
•
Check with Software Configurator the presence of voltage from the grid (230 V)
•
Check the correct installation and wiring of the Power Meter (make sure that the cable
does not get disturbed and use a "twisted" and shielded upper category cable)
•
Check that the supply fuse is not interrupted (central LED must be fixed)
•
Check with Software Configurator that the mains voltage is between 210 and 250 V and
the network frequency between 49 and 51 Hz
•
Check that there is no alarm in the "trend" table (battery thermal alarm, supply or charger)
•
Check in the "Advanced" tab that there is no internal alarm or "battery fault". If present,
click on "Reset Charge Fault"
SOLAR ECLIPSE DOES NOT CHARGE BATTERIES (zero charge power in charge)
•
Verify that Solar Eclipse is "STARTED" (first left LED on)
•
Connect to interface 485 and start Software Configurator
•
Shut off loads
•
Enable the green line "Grid Power"
in the “Trend” tab and check for negative values < 100
W (line below zero)
•
If the green line is above zero and the PV system is producing more than the
consumption of the user, check the position of the network sensor (Power Meter)
•
Verify that the "String Power" is greater than 100 W
•
Verify that "String Voltage" with inverter operating is compatible with the number of
modules set in the Software Configurator at configuration stage (see table 8. eg: 8
modules set to 30 x 8 = 240 V)
•
Verify that the battery percentage is < 90%
•
If the "Batt. Charging" light turns green and
“Battery Power” does not increase (positive
values - red Line over Zero) Contact P800 SRL Technical Support