5
Table 1. Service parameter's list
Disp.
Parameter
Min Max Step Factory
default
Π100 Fan max work power or max power when Πr 0-10.
50
100 10%
100
n 40 Minimum fan power.
20
40
10%
40
Πh 2 Fan speed decrease coefficient.
2
10
1
2
Πr 1 Automatic fan speed control and time of fan start.
--, 0
10
1
1
Πn 5 Fan work time.
--, 5
60
1s
5
Πu 6 Fan pause time.
1
99 1min
6
P 42 Central heating pump launch temperature.
30
70
1ºC
42
Ph 2 Central heating pump hysteresis.
1
10
1ºC
2
Pc 2 The work mode and pause time of CH pump.
--, 1 99, F 1min
2
L 40 Minimum boiler temperature.
30
65
1ºC
40
H 85 Maximum boiler temperature.
80
90
1ºC
85
h 2
Boiler temperature hysteresis.
1
10
1ºC
2
A 99 Boiler overheating temperature.
90
99
1ºC
99
Fd60 Fuel shortage testing time with burning.
--, 1 99, 4h 1min
60
Fb30 Fuel shortage testing time in WORK mode and
burning out.
--, 1 99, 4h 1min
30
Ar 0
Work mode of extra output:
0– output turning on extra boiler,
1– alarm output,
2– output controlling mixing valve,
3– output controlling emergency cooling system,
4– output controlling extra devices turning on during
work of blow-in fan.
0
4
1
0
Prod Return to factory defaults after pressing OK
outP Central heating pump testing, press OK - launch
outP out1
outΠ Fan output testing, press OK - launch
outΠ out2
outr
Additional output testing, press OK - launch
outr out3
End Exit the service mode after pressing OK
In the table above, the first column represents example display indications, in the next
columns there are: parameter description, minimal amount, maximum amount allowed
to set, step of the parameter during the setup, factory defaults, to which you can return
by choosing [Prod] option.
4.1. Pressure fan work parameters.
Fan power [Π100]
– this value defines power of the fan. When „Πr”parameter is set to
„0-10” this is the maximum power of the fanwhich can be achieved during automatic
fan control.
Minimum fan power [n 40]
– lowest fan power which can be used when automatic
fan speed control is on and when fan speed is gradually increased during boiler start.
Fan speed decrease coefficient [Πh 2]
– this parameter influences the way fan
speed is reduced when boiler tremperature is approaching its desired value. E.g.
setting this parameter to 2 means that when the controller is in WORK mode and