Connection to power supply
The fan is supplied without a plug but with all of the internal electrical connections.
NB: The motor is 380 V
Black = Phase 1
Yellow/Green = Earth
Brown = Phase 2
White = Phase 3
If the fan rotates in the wrong direction, swap phase 2 and 3.
When the fan is installed, a control panel must be fitted in accordance with the
requirements in EN 60439-1 EN and the conductors must be connected in accordance
with the standards EN 60204-1 and EN 60364.
The panel must be equipped with the following components:
Lockable isolating switch.
Magnetic thermal switch. This may be
necessary, depending on the electrical
system that the fan is to be connected
to. It is the responsibility of the
installation technician to assess the
requirements.
Approved emergency stop. When
activated, the emergency stop must
disconnect the power from the motor.
Start/stop button.