Press
to highlight the fiber optic cabling standard, then press
to SELECT.
Press
to highlight the fiber type of the network under test, then press
to SELECT.
Press
to use measure the fiber length with the Fiber OWL 4 BOLT, or to enter the length
manually, press
and skip to
.
Connect the Fiber OWL 4 BOLT to your fiber link as shown in Figure 5, then press
to
continue.
Review the end-to-end fiber length, then press
to continue. In the example screenshot at
right, the end-to-end fiber length could be within the range of 1000 to 1006 meters.
The end-to-end length shown here is the length that will be entered into the Link Wizard
configuration. Press
to continue.
OPTIONAL:
you may also enter the fiber length manually from this screen.
If unsure about which cabling standard to use, select TIA-568-B.3.
Length testing is complete. You may now remove all of the patch cables from the link under test.
F1
F2
F1
F2
1
ABC
2
DEF
F1
F2
DONE
QUICK REFERENCE GUIDES
PAGE 4 OF 6
[1 TO 65535]
<---
UNITS
--->
[01000] METERS
ENTER FIBER LENGTH:
_____________________
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
FIGURE 5
Fiber OWL 4 BOLT
Length Test Connection
50 0um MultiMode
NEXT
SELECT
OUTDOOR SingleMode
FIBER TYPES
_____________________
INDOOR SingleMode
62 5um MultiMode
USER DEFINED #1
USER DEFINED #2
NEXT
SELECT
ISO/IEC 11801
FIBER STANDARDS
_____________________
TIA-568B 3/CAN-T529
<1> USE THE METER TO
MEASURE LENGTH
<2> ENTER LENGTH
FIBER LENGTH METHOD
MANUALLY
FIBER A
FIBER B
PATCH FIBER A TO
DONE
END OF THE LINK
^
CONNECT
^
_____________________
FIBER B AT THE FAR
(FIBER PAIR REQUIRED)
FIBER LENGTH
01000 -0/+6 meters
TEST
DONE
INDEX
1310nm Index(n)=1 490
_____________________
LIGHT SOURCE CONNECTOR
PORT NOTES:
– CONNECTOR TYPE MAY VARY
– DO NOT INSERT ANGLED
PHYSICAL CONTACT (APC)
CONNECTOR
Optical Power Meter:
Fiber OWL 4
Fiber Optic Light Source:
DUAL OWL Series Multimode Sources