Force Settings:
Force settings are pre-programmed at the factory to force level 6 (See Chart Below) and applied during the Open/Closed Limit settings steps. For
normal use, these settings should not need adjustment.
Conditions possibly requiring adjustments are:
1. Doors with very stiff weather seals.
2. Doors that start down, STOP, and reverse before closing.
3. Doors that start up, but STOP before they completely open.
AVERTISSEMENT
!
Pour éviter les blessures ou des dommages
•
NE JAMAIS
régler la force pour compenser des
dommages, y compris une porte mal équilibrée, un rail
de porte coinçant ou des ressorts cassés.
•
Tous les mois, EFFECTUEZ LE TEST D’INVERSION AU
CONTACT.
WARNING
!
TO AVOID INJURY OR DAMAGE
•
NEVER
adjust the force settings to adjust for damage,
including an unbalanced door, binding door track or
broken spring.
•
Perform a CONTACT REVERSE TEST monthly.
1. Press and hold
both UP & DOWN arrow buttons until the ROUND LED turns RED. Release
buttons.
•
LEDs will show current force level. SEE CHART.
2. Press either the UP or DOWN arrow button until the desired
UP
force setting is shown. SEE
CHART.
3. Press & release the PRGM button to lock the desired
UP
FORCE setting.
•
Both LEDs will turn BLUE then go out confirming that the UP force setting has been
changed and is locked.
•
LEDs will now show the current
DOWN
FORCE setting. SEE CHART.
4. Press either the UP or DOWN arrow button until desired
DOWN
force setting is shown. SEE
CHART.
5. Press & release the PRGM button to lock the desired
DOWN
FORCE setting.
•
Both LEDs will turn BLUE then go out confirming that the DOWN force setting has been
changed and is locked.
6. Perform all steps on page 20 to test operator.
RED
PRESS & RELEASE
See Chart for
Force level
indicators.
Press PRGM to
lock settings
FORCE SETTING CHART
Force Level
Long LED
Round LED
1 (LOWEST)
OFF
BLUE
2
BLUE
OFF
3
BLUE
BLUE
4
OFF
PURPLE
5
PURPLE
OFF
6
PURPLE
PURPLE
7
OFF
RED
8
RED
OFF
9 (HIGHEST)
RED
RED
CAUTION
!
DO NOT adjust force level above what is necessary to
allow for normal door operation.
CAUTION
!
NE réglez PAS la force à un niveau supérieur à ce qui est
nécessaire pour permettre un fonctionnement normal de
porte.
CHANGING FORCE SETTINGS
IMPORTANT NOTICE
IF FORCE SETTING IS ALTERED, ALL STEPS ON PAGE 20 MUST BE PERFORMED TO LOCK IN THE FORCE PROFILE
FOR PROPER DOOR OPERATION.
!
!
SPECIAL INSTALLATION INFORMATION